GE Masoneilan 12420 Instruction Manual & Safety Manual page 58

Masoneilan 12400 series. level transmitter/controller
Table of Contents

Advertisement

Message on
LCD / ValVue
(English))
TEMPERATURE
Compensated temperature reading of
SENSOR OF
sensor circuit board was outside the -55 °C
SENSOR BOARD
(-67 °F) to +125 °C (+257 °F) for five reads in
a row
NVM CHECKSUM
Non Volatile Memory checksum error of
SENSOR READ
sensor circuit board
NVM MODULE
Non Volatile Memory error of main circuit
WRITE
board module if write to FRAM failed or if
data repairing in FRAM failed
NVM SENSOR
Non Volatile Memory error of sensor
WRITE
circuit board if write to FRAM failed or if
data repairing in FRAM failed
NVM MODULE
Non Volatile Memory error of main circuit
TEST
board module if both an FRAM record and
its copy have CRC errors
NVM SENSOR
Non Volatile Memory error of sensor
TEST
circuit board if both a FRAM record and its
copy have CRC errors
RAM CHECKSUM
RAM checksum error
ERROR
FLASH
Flash checksum error
CHECKSUM
ERROR
RTOS
A RTOS task overran itself
SCHEDULING
ERROR
STACK ERROR
Stack error.
A valid hidden record (in RAM) existing
upon reset indicating that a stack
overflow has occurred, as detected by the
task switching code
FACTORY WRITE
Raw write to FRAM
WATCHDOG
Device recovered after reset
TIMEOUT
IRQ FAULT
Valid hidden record (in FRAM) existing
upon reset that indicates that an illegal
interrupt occurred
TIMEOUT FLASH
Time to complete the whole flashing
TEST
process is over
56 | GE Oil & Gas
Description
Probable Cause
Environment
Ambient temperature exceeded operating
temperature range
Permanent corruption of the content in
non-volatile memory occurred
A problem occurred when attempting to
write to the non-volatile memory
A problem occurred when attempting to
write to the non-volatile memory
A problem occurred when testing the
non-volatile memory
A problem occurred when testing the
non-volatile memory
A corruption of the content in non-volatile
memory occurred
The firmware checksum was invalid due
to data corruption
The micro-controller failed an operation
A problem with the memory stack
occurred
Raw write to FRAM
Technical fault to indicate a factory-only
operation
Device recovered after reset
An illegal circuit board interrupt occurred
This message appears if a round of flash
test is not completed in 2 hours
® 2014 General Electric Company. All rights reserved.
Recommended Action
Take any action to ensure
temperature does not exceed
normal temperature range.
Return the unit if it fails
Remove power to the device for two
minutes and restart the device
If the failure persists, replace the
device
Clear the condition using ValVue
software or HART host
If the failure persists, replace the
device
Clear the condition using ValVue
software or HART host
If the failure persists, replace the
device
Clear the condition using ValVue
software or HART host
Clear the condition using ValVue
software or HART host
Remove power to the device for 2
minutes and restart the device
If the failure persists, replace the
device
Clear the condition using ValVue
software or HART host
Clear the condition using ValVue
software or HART host
Clear the condition using ValVue
software or HART host
If the failure persists, replace the
device
Clear the condition using ValVue
software or HART host
If the failure persists, replace the
device