10. Troubleshooting

10.1. NO SIGNAL

Check connection wires to 12400 Series instrument.
Check polarities of the connection wires.

10.2. EXISTING SIGNAL BUT NOTHING ON LCD DISPLAY

The electronic module might be damaged and must be replaced at factory.

10.3. STEADY SIGNAL, NO CHANGE WHEN LEVEL VARIES

In case of external mounting (see Section 4.2.1), check that displacer lock up in the displacer chamber, made for
transportation purpose, has been removed.
Check the instrument is not in FAILSAFE mode.
Check the device is in NORMAL operating mode (alternating display of signal and level variable).
Check correct coupling between transmission rod and mechanism sub-assembly by moving flexure (59), which allows
simulating a level change.
Check that the correct supply voltage is applied to terminal blocks of main analog output connections (AO_1).

10.4. OUTPUT SIGNAL DIFFERS FROM VALUE DISPLAYED ON LCD

FULL COMPLIANCE WITH STANDARDS REQUIREMENTS RELATED TO INTRUMENTS INSTALLED
Check the load resistance is compliant with Section 5.4.5 and the power supply applied to main analog output signal is
greater than 10 VDC.
Insert a reference milliamp meter in series with the 4-20 mA signal loop.
To recalibrate the internal milliamp meter, enter the [VAR SET] sub-menu via the ADVANCED SETUP menu (see
Appendix C).
Enter into [MA LOW:mA]. Decrease or increase value (ranges from 2900 to 3500 by increment one) until the
o
reference milliamp meter indicates 4.000mA (see Appendix C).
Enter into [MA HI:mA]. Decrease or increase value (ranges from 2900 to 3500 by increment one) until the reference
o
milliamp meter indicates 20.000mA (see Appendix C).
Enter into [SIG GENE] via the ADVANCED SETUP menu to generate various output signals and check the current
o
signal versus the reference milliamp meter (see Appendix E).
® 2014 General Electric Company. All rights reserved.
WARNING:
IN HAZARDOUS AREAS MUST BE ENSURED.
Masoneilan 12400 Series Transmitter/Controller Instruction Manual | 53