Chapter 1. General Information; Introduction; Associated Publications; Epg Models - Woodward EPG 524 Installation And Troubleshooting Manual

Epg electrically powered governor without position feedback
Table of Contents

Advertisement

Manual 82329
Each Woodward Electrically Powered Governor (EPG) system includes three
basic parts:
A magnetic pickup (MPU) which senses engine speed from an engine-
driven gear.
A speed control which receives the speed signal from the MPU, compares it
to a reference signal, and generates a control signal which the control sends
to the actuator.
An actuator which receives the signal from the control and positions its
output shaft according to this signal. The output shaft is linked to the fuel
control.
There are two EPG models:
The isochronous speed control, which is available with start-fuel limit or dual
dynamics;
The droop speed control, which includes a load sensor and provides droop
control for generator sets.
Different actuator sizes are available for different work output requirements.
Models are available for either 12 or 24 volt systems.
Manual
Title
82313
Generator Load Sensor
25070
Electronic Control Installation Guide
82510
Magnetic Pickups & Proximity Switches for Electronic Controls
82493
Isochronous EPG
82327
EPG with Droop
82476
Ramp Generator
Product
Spec.
Title
04106
EPG Electrically Powered Governors
82314
Generator Load Sensor
Model
512
524
1712
1724
Woodward
Chapter 1.
General Information

Introduction

Associated Publications

EPG Models

Battery
Work
Voltage
Output
10–16 V
0.7 J (0.5 ft-lb)
20–32 V
1.0 J (0.75 ft-lb)
10–16 V
1.6 J (1.2 ft-lb)
20–32 V
2.3 J (1.7 ft-lb)
EPG Electrically Powered Governor