Physical And Operational Specifications; Specifications And References - GE SVI II AP-2 Quick Start Manual

Svi ii ap digital positioner
Table of Contents

Advertisement

Specifications and
References

Physical and Operational Specifications

This section provides the physical and operational specifications for the SVI II AP.
Operating Temperature Limits
Storage Temperature Limits
Temperature Effect
Supply Pressure Effect
Relative Humidity
Humidity Effect
Insulation Resistance
MTBF
Electromagnetic Compatibility
Electrostatic
Fast Transient Burst
Vibration Influence
Measured at SVI II AP Housing
Magnetic Field Influence
Table 9 Environmental Specifications
-58° F to 185° F (-50° C to 85° C)
-58° F to 200° F (-50° C to 93° C)
< 0.005% / °F typical; -40° F to 180° F (< 0.01% / °C typical;
-40° C to 82° C)
0.05% per psi (.73% per bar)
10 to 90% non-condensing
Less than 0.2% after 2 days at 104 °F (40° C), 95% Relative
Humidity.
Greater than 10 G Ohms at 50% RH.
49 years based on MIL handbook calculation for electronic parts
and field data on mechanical parts
Electrostatic discharge — No effect with contact discharge level of
4KV and air discharge level of 8 kV
(IEC 1000-4-2)
Radio frequency interference — Less than 0.2% at 10 V per meter
(EN 50140)
No effect at 2 kV (Coupling clamp IEC 1000-4-4).
4 mm at 5 - 15 Hz - Negligible
2 G at 15 - 150 Hz Less than 2 % of span
1 G at 150 - 2000 Hz - Less than 2% of span
Negligible at 30 A/m (EN61000-4-8)
CE MARK certified to EN50081-2 and EN50082-2
65
A

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Svi ii ap-3

Table of Contents