Check Out,
2. Adjust current to 12 mA. On initial power up of a newly installed SVI II AP, the
positioner runs in NORMAL mode using the default instrument parameters
installed at the factory. The positioner cycles through the NORMAL cycle
menu and LCD displays the following values:
3. Proceed to Configuration and Calibration.
* For firmware version 3.2.1, the supply pressure appears on the LCD.
Additionally, Stops results and Autotune results, stay displayed until cleared.
NOTE
PRES: Pressure - unit of measurement and value*
SIGNAL
POS (Position)
An exclamation point (!) appears in the top left corner of the display
window to indicate that there is further instrument status available.
If the SVI II AP is specified without local pushbuttons and
display, local operation is not available. Configure and
calibrate with ValVue and a HART modem.
51
Powering Up the SVI II AP