Configuration with Pushbuttons
Check Out,
Configuration Menu
Because calibration depends on certain configuration options you must perform
Configuration before you perform Calibration when installing the SVI II AP for the
first time.
If a change is made in the Air-to-Open / Air-to-Close configuration option or if you
move the SVI II AP to a different valve or make any change to the valve position
linkage, you must run the find STOPS calibration again.
Figure 28 CONFIGure Menu
53