___________________ Preface ___________________ Guide to the documentation ___________________ SIMATIC New properties ___________________ Product overview ET 200SP BaseUnits ___________________ (6ES7193-6BP.../3RK1908-0AP00…) BaseUnits for I/O modules ___________________ BaseUnits for motor starters Manual ___________________ Potential distributor modules ___________________ Dimension drawings of I/O modules ___________________ Dimension drawings of motor starters ___________________...
Page 3
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Preface Purpose of the documentation This manual supplements the system manual ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293). Functions affecting the system in general are described there. The information provided in this manual and in the system/function manuals supports you in commissioning the system.
Page 5
Siemens' products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customers' exposure to cyber threats.
Table of contents Preface ..............................3 Guide to the documentation ........................8 New properties ............................13 Product overview ..........................14 BaseUnits for I/O modules ........................21 Product description ......................... 21 4.1.1 Introduction ..........................21 BU type A0, light-colored version with AUX terminals ............22 4.2.1 Product overview ........................
Page 7
Table of contents 4.10 BU type B0, dark-colored version, with AUX terminals, supply over P1, P2 busbar ..... 56 4.10.1 Product overview........................56 4.10.2 Connecting ..........................57 4.10.3 Technical specifications ......................58 4.11 BU type B1, dark-colored version, without AUX terminals, supply over supply terminals ..60 4.11.1 Product overview........................
Page 8
Table of contents BU30-MS3 - BaseUnit with 24 V DC infeed................96 5.4.1 Product overview ........................96 5.4.2 Connection ..........................97 5.4.3 Technical specifications ......................99 BU30-MS4 - BaseUnit without infeed ................... 100 5.5.1 Product overview ........................100 5.5.2 Connection ..........................101 5.5.3 Technical specifications ......................
Guide to the documentation The documentation for the SIMATIC ET 200SP distributed I/O system is arranged into three areas. This arrangement enables you to access the specific content you require. Basic information The system manual describes in detail the configuration, installation, wiring and commissioning of the SIMATIC ET 200SP.
Page 10
You can download the product information free of charge from the Internet (https://support.industry.siemens.com/cs/ww/de/view/109742709). Manual Collection ET 200SP The Manual Collection contains the complete documentation on the SIMATIC ET 200SP distributed I/O system gathered together in one file. You can find the Manual Collection on the Internet (http://support.automation.siemens.com/WW/view/en/84133942).
Page 11
● Manuals, characteristics, operating manuals, certificates ● Product master data You can find "mySupport" - CAx Data in the Internet (http://support.industry.siemens.com/my/ww/en/CAxOnline). Application examples The application examples support you with various tools and examples for solving your automation tasks. Solutions are shown in interplay with multiple components in the system - separated from the focus in individual products.
Page 12
You can find the SIMATIC Automation Tool on the Internet (https://support.industry.siemens.com/cs/ww/de/view/109751152). PRONETA With SIEMENS PRONETA (PROFINET network analysis), you analyze the plant network during commissioning. PRONETA features two core functions: ● The topology overview independently scans PROFINET and all connected components.
Page 13
Guide to the documentation SINETPLAN SINETPLAN, the Siemens Network Planner, supports you in planning automation systems and networks based on PROFINET. The tool facilitates professional and predictive dimensioning of your PROFINET installation as early as in the planning stage. In addition, SINETPLAN supports you during network optimization and helps you to exploit network resources optimally and to plan reserves.
New properties What's new in the BaseUnits manual, edition 02/2018, compared to edition 12/2016? What's new? What are the customer benefits? Where can I find infor- mation? Potential distributor A system-integrated potential distribu- Section Potential distrib- contents modules tion can be implemented via the utor modules (Page 113) PotDis modules.
Product overview General properties of the BaseUnits The ET 200SP distributed I/O system includes various BaseUnits. You use the BaseUnit to specify the following, for example: ● Process connection ● Plug-in I/O module/motor starter ● Infeed of supply voltage specified You can recognize the properties of the BaseUnits from their short description: Table 3- 1 Properties of the BaseUnits...
Page 16
Product overview Short description BU15-P16+A10+2D/T BaseUnit properties (example) Self-assembling voltage 2 push-in terminals for supplying or tapping the supply buses voltage via the self-assembling voltage buses P1, P2 (see D, B) 2 push-in terminals for supplying or tapping the • supply voltage via the self-assembling voltage buses P1, P2 (see D, B) 2×5 push-in additional terminals (1 B to 5 B, 1 C to...
Page 17
Product overview Properties of the BaseUnits for motor starters The following table lists the properties of the individual BaseUnits for motor starters: BaseUnit Properties BU30-MS1 Push-in terminals for opening a new potential group (24 V DC). • Feeding in of supply voltage up to a maximum supply current of 7 A •...
Page 18
Product overview Properties of the potential distributor modules The following table shows the properties of the individual potential distributor modules: Table 3- 2 PotDis-BaseUnits properties Short description PotDis-BU-P1/D-R PotDis-BaseUnit properties (example) Designation PotDis-BU PotDis-BaseUnit Process connection Terminals for supplying or tapping the supply voltage with connection to the voltage bus P1 (see D, B) (24 V DC / 10 A) Terminals for supplying or tapping the supply voltage...
Page 19
Product overview Properties of the terminal blocks PotDis-TB The following table shows the properties of the individual terminal blocks: Table 3- 3 Properties of the PotDis-Terminalblocks Short description PotDis-TB-P1-R (example) PotDis-Terminalblock properties Designation PotDis-TB PotDis terminal block Process connection Connection to the voltage bus P1 •...
Page 20
Proper use of hardware products This equipment is only allowed to be used for the applications described in the catalog and in the technical description, and only in conjunction with non-Siemens equipment and components recommended by Siemens. Correct transport, storage, installation and assembly, as well as careful operation and maintenance, are required to ensure that the product operates safely and without faults.
Page 21
Siemens Newsletter (http://www.industry.siemens.com/newsletter) Sign on to the following newsletter under "Products & Solutions": • Control Components and System Engineering News •...
● The infeed of protective conductor via BU is not permitted. You can find additional information on using the BaseUnit in the ET 200SP System Manual (https://support.industry.siemens.com/cs/ww/en/view/58649293). Note All BaseUnits placed in a load group must match the infeed potential of the corresponding light-colored BaseUnits.
BaseUnits for I/O modules 4.2 BU type A0, light-colored version with AUX terminals BU type A0, light-colored version with AUX terminals Short designation Short designation: BU15-P16+A10+2D 4.2.1 Product overview Delivery options (packing unit VPE) 6ES7193-6BP20-0DA0 (VPE: 1 unit) 6ES7193-6BP20-2DA0 (VPE: 10 units) View Figure 4-1 BU type A0, light-colored version with AUX terminals...
● Connection system in the form of push-in terminals Connection cross-sections are available in the ET 200SP System Manual (https://support.industry.siemens.com/cs/ww/de/view/58649293). Maximum configuration per potential group The number of I/O modules that can be used per potential group depends on the following factors: 1.
BaseUnits for I/O modules 4.2 BU type A0, light-colored version with AUX terminals Block diagram ① Backplane bus ② I/O module ③ Terminals with connection to the I/O module ④ System-integrated, self-assembling voltage buses P1, P2 with connection to the supply termi- nals, interrupted to the adjacent module on the left (forms a new potential group) ⑤...
Page 26
BaseUnits for I/O modules 4.2 BU type A0, light-colored version with AUX terminals Article number 6ES7193-6BP20-2DA0 Hardware configuration Formation of potential groups New potential group • Potential group continued from the left • Potential separation between the potential groups Isolation Isolation tested with 707 V DC (type test) Accessories...
BaseUnits for I/O modules 4.3 BU type A0, light-colored version without AUX terminals BU type A0, light-colored version without AUX terminals Short designation Short designation: BU15-P16+A0+2D 4.3.1 Product overview Delivery options (packing unit VPE) 6ES7193-6BP00-0DA0 (VPE: 1 unit) 6ES7193-6BP00-2DA0 (VPE: 10 units) View Figure 4-3 BU type A0, light-colored version, without AUX terminals...
● Connection system in the form of push-in terminals Connection cross-sections are available in the ET 200SP System Manual (https://support.industry.siemens.com/cs/ww/de/view/58649293). Maximum configuration per potential group The number of I/O modules that can be used per potential group depends on the following factors: 1.
BaseUnits for I/O modules 4.3 BU type A0, light-colored version without AUX terminals Block diagram ① Backplane bus ② I/O module ③ Terminals with connection to the I/O module ④ System-integrated, self-assembling voltage buses P1, P2 with connection to the supply termi- nals, interrupted to the adjacent module on the left (forms a new potential group) ⑤...
Page 30
BaseUnits for I/O modules 4.3 BU type A0, light-colored version without AUX terminals Article number 6ES7193-6BP20-2DA0 Hardware configuration Formation of potential groups New potential group • Potential group continued from the left • Potential separation between the potential groups Isolation Isolation tested with 707 V DC (type test) Accessories...
BaseUnits for I/O modules 4.4 BU type A0, dark-colored version, with AUX terminals BU type A0, dark-colored version, with AUX terminals Short designation Short designation: BU15-P16+A10+2B 4.4.1 Product overview Delivery options (packing unit VPE) 6ES7193-6BP20-0BA0 (VPE: 1 unit) 6ES7193-6BP20-2BA0 (VPE: 10 units) View Figure 4-5 BU type A0, dark-colored version, with AUX terminals...
● 10 AUX terminals for connecting a protective conductor or potential. The AUX busbar is not connected to the I/O module. Max. 24 V DC/10 A ● Connection system in the form of push-in terminals Connection cross-sections are available in the ET 200SP System Manual (https://support.industry.siemens.com/cs/ww/de/view/58649293). 4.4.2 Connection Pin assignment...
BaseUnits for I/O modules 4.4 BU type A0, dark-colored version, with AUX terminals Block diagram ① Backplane bus ② I/O module ③ Terminals with connection to the I/O module ④ System-integrated, self-assembling voltage buses P1, P2 with connection to the supply termi- nals, connected to the adjacent module on the left ⑤...
Page 34
BaseUnits for I/O modules 4.4 BU type A0, dark-colored version, with AUX terminals Article number 6ES7193-6BP20-0BA0 Hardware configuration Formation of potential groups New potential group • Potential group continued from the left • Isolation Isolation tested with 707 V DC (type test) Accessories Color coding labels CC00 to CC09...
BaseUnits for I/O modules 4.5 BU type A0, dark-colored version, without AUX terminals BU type A0, dark-colored version, without AUX terminals Short designation Short designation: BU15-P16+A0+2B 4.5.1 Product overview Delivery options (packing unit VPE) 6ES7193-6BP00-0BA0 (VPE: 1 unit) 6ES7193-6BP00-2BA0 (VPE: 10 units) View Figure 4-7 BU type A0, dark-colored version, without AUX terminals...
● No access to the AUX busbar via terminals ● 16 terminals to the process (assignment through the I/O module) ● Connection system in the form of push-in terminals Connection cross-sections are available in the ET 200SP System Manual (https://support.industry.siemens.com/cs/ww/de/view/58649293). 4.5.2 Connection Pin assignment...
BaseUnits for I/O modules 4.5 BU type A0, dark-colored version, without AUX terminals Block diagram ① Backplane bus ② I/O module ③ Terminals with connection to the I/O module ④ System-integrated, self-assembling voltage buses P1, P2 with connection to the supply termi- nals, connected to the adjacent module on the left ⑤...
Page 38
BaseUnits for I/O modules 4.5 BU type A0, dark-colored version, without AUX terminals Article number 6ES7193-6BP00-0BA0 Isolation Isolation tested with 707 V DC (type test) Accessories Color coding labels CC00 to CC09 for process terminals • does not exist for AUX terminals •...
BaseUnits for I/O modules 4.6 BU type A1, light-colored version, with additional terminals BU type A1, light-colored version, with additional terminals Short designation Short designation: BU15-P16+A0+12D/T 4.6.1 Product overview Delivery options (packing unit VPE) 6ES7193-6BP40-0DA1 (VPE: 1 unit) View Figure 4-9 BU type A1, light-colored version, with additional terminals BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 02/2018, A5E03727049-AJ...
Page 40
● Connection system in the form of push-in terminals Connection cross-sections are available in the ET 200SP System Manual (https://support.industry.siemens.com/cs/ww/de/view/58649293). Maximum configuration per potential group The number of I/O modules that can be used per potential group depends on the following factors: 1.
1 to 16 Assignment is determined by the I/O module. You can find additional infor- mation in the I/O Module (http://support.automation.siemens.com/WW/view/en/55679691/133300) manual. 1 B, 2 B, 3 B, 4 B, 2 x 5 add-on terminals for the infeed of a supply voltage up to 24 V DC with 5 B / max.
BaseUnits for I/O modules 4.6 BU type A1, light-colored version, with additional terminals Block diagram ① Backplane bus ② I/O module ③ Internal reference junction for temperature compensation ④ Terminals with connection to the I/O module ⑤ Additional terminals for feeding an additional supply voltage ⑥...
Page 43
BaseUnits for I/O modules 4.6 BU type A1, light-colored version, with additional terminals Article number 6ES7193-6BP40-0DA1 Current carrying capacity For P1 and P2 bus, max. 10 A For process terminals, max. Hardware configuration Additional terminals Temperature sensor Formation of potential groups New potential group •...
BaseUnits for I/O modules 4.7 BU type A1, light-colored version, without additional terminals BU type A1, light-colored version, without additional terminals Short designation Short designation: BU15-P16+A0+2D/T 4.7.1 Product overview Delivery options (packing unit VPE) 6ES7193-6BP00-0DA1 (VPE: 1 unit) View Figure 4-11 BU type A1, light-colored version, without additional terminals BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 02/2018, A5E03727049-AJ...
Page 45
● Connection system in the form of push-in terminals Connection cross-sections are available in the ET 200SP System Manual (https://support.industry.siemens.com/cs/ww/de/view/58649293). Maximum configuration per potential group The number of I/O modules that can be used per potential group depends on the following factors: 1.
Terminal Descriptions 1 to 16 Assignment is determined by the I/O module. You can find additional infor- mation in the I/O Module (http://support.automation.siemens.com/WW/view/en/55679691/133300) manual. (AUX) No access to the AUX busbar via terminals L+, P1 / M, P2 L+: Rated supply voltage 24 V DC with max. 10 A...
BaseUnits for I/O modules 4.7 BU type A1, light-colored version, without additional terminals 4.7.3 Technical specifications Technical specifications of the BU type A1, light-colored version, without additional terminals Article number 6ES7193-6BP00-0DA1 General information Product type designation Type A1 Supply voltage Rated value (DC) 24 V external protection for power supply lines...
Page 48
BaseUnits for I/O modules 4.7 BU type A1, light-colored version, without additional terminals Article number 6ES7193-6BP00-0DA1 Dimensions Width 15 mm Height 117 mm Depth 35 mm Weights Weight, approx. 40 g BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 02/2018, A5E03727049-AJ...
BaseUnits for I/O modules 4.8 BU type A1, dark-colored version, with additional terminals BU type A1, dark-colored version, with additional terminals Short designation Short designation: BU15-P16+A0+12B/T 4.8.1 Product overview Delivery options (packing unit VPE) 6ES7193-6BP40-0BA1 (VPE: 1 unit) View Figure 4-13 BU type A1, dark-colored version, with additional terminals BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 02/2018, A5E03727049-AJ...
● Recording of the terminal temperature for internal temperature compensation at connected thermocouples ● Connection system in the form of push-in terminals Connection cross-sections are available in the ET 200SP System Manual (https://support.industry.siemens.com/cs/ww/de/view/58649293). 4.8.2 Connection Pin assignment Pin assignment for BU type A1, dark-colored version, with additional terminals...
BaseUnits for I/O modules 4.8 BU type A1, dark-colored version, with additional terminals Block diagram ① Backplane bus ② I/O module ③ Internal reference junction for temperature compensation ④ Terminals with connection to the I/O module ⑤ Additional terminals for feeding an additional supply voltage ⑥...
Page 52
BaseUnits for I/O modules 4.8 BU type A1, dark-colored version, with additional terminals Article number 6ES7193-6BP40-0BA1 Current carrying capacity For P1 and P2 bus, max. 10 A For process terminals, max. Hardware configuration Additional terminals Temperature sensor Formation of potential groups New potential group •...
BaseUnits for I/O modules 4.9 BU type A1, dark-colored version, without additional terminals BU type A1, dark-colored version, without additional terminals Short designation Short designation: BU15-P16+A0+2B/T 4.9.1 Product overview Delivery options (packing unit VPE) 6ES7193-6BP00-0BA1 (VPE: 1 unit) View Figure 4-15 BU type A1, dark-colored version, without additional terminals BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 02/2018, A5E03727049-AJ...
● Recording of the terminal temperature for internal temperature compensation at connected thermocouples ● Connection system in the form of push-in terminals Connection cross-sections are available in the ET 200SP System Manual (https://support.industry.siemens.com/cs/ww/de/view/58649293). 4.9.2 Connection Pin assignment Pin assignment for BU type A1, dark-colored version, without additional terminals...
BaseUnits for I/O modules 4.9 BU type A1, dark-colored version, without additional terminals Block diagram ① Backplane bus ② I/O module ③ Internal reference junction for temperature compensation ④ Terminals with connection to the I/O module ⑤ System-integrated, self-assembling voltage buses P1, P2 with connection to the supply termi- nals, connected to the adjacent module on the left ⑥...
Page 56
BaseUnits for I/O modules 4.9 BU type A1, dark-colored version, without additional terminals Article number 6ES7193-6BP00-0BA1 Formation of potential groups New potential group • Potential group continued from the left • Isolation Isolation tested with 707 V DC (type test) Accessories Color coding labels CC00 to CC09...
BaseUnits for I/O modules 4.10 BU type B0, dark-colored version, with AUX terminals, supply over P1, P2 busbar 4.10 BU type B0, dark-colored version, with AUX terminals, supply over P1, P2 busbar Short designation Short designation: BU20-P12+A4+0B 4.10.1 Product overview Delivery options (packing unit VPE) 6ES7193-6BP20-0BB0 (VPE: 1 unit) 6ES7193-6BP20-2BB0 (VPE: 10 units)
● Access to the AUX busbar via terminals ● 12 terminals to the process (assignment with the I/O module) ● Connection system in the form of push-in terminals Connection cross-sections are available in the ET 200SP System Manual (https://support.industry.siemens.com/cs/ww/de/view/58649293). 4.10.2 Connecting Pin assignment...
BaseUnits for I/O modules 4.10 BU type B0, dark-colored version, with AUX terminals, supply over P1, P2 busbar Block diagram ① Backplane bus ② I/O module ③ Terminals with connection to the I/O module ④ System-integrated, self-assembling voltage buses P1, P2 with connection to the supply termi- nals, connected to the adjacent module on the left ⑤...
Page 60
BaseUnits for I/O modules 4.10 BU type B0, dark-colored version, with AUX terminals, supply over P1, P2 busbar Article number 6ES7193-6BP20-0BB0 Isolation Isolation tested with 3 250 V DC Dimensions Width 20 mm Height 117 mm Depth 35 mm Weights Weight, approx.
BaseUnits for I/O modules 4.11 BU type B1, dark-colored version, without AUX terminals, supply over supply terminals 4.11 BU type B1, dark-colored version, without AUX terminals, supply over supply terminals Short designation Short designation: BU20-P12+A0+4B 4.11.1 Product overview Delivery options (packing unit VPE) 6ES7193-6BP20-0BB1 (VPE: 1 unit) 6ES7193-6BP20-2BB1 (VPE: 10 units) View...
● No access to the power and AUX busbars via terminals ● 12 terminals to the process (assignment with the I/O module) ● Connection system in the form of push-in terminals Connection cross-sections are available in the ET 200SP System Manual (https://support.industry.siemens.com/cs/ww/de/view/58649293). 4.11.2 Connecting up Pin assignment...
BaseUnits for I/O modules 4.11 BU type B1, dark-colored version, without AUX terminals, supply over supply terminals Block diagram ① Backplane bus ② I/O module ③ Terminals with connection to the I/O module ④ System-integrated, self-assembling voltage buses P1, P2 without connection to the terminals, connected to the adjacent module on the left ⑤...
Page 64
BaseUnits for I/O modules 4.11 BU type B1, dark-colored version, without AUX terminals, supply over supply terminals Article number 6ES7193-6BP20-0BB1 Potential separation between backplane bus and supply voltage between process terminals and supply voltage between power bus and supply voltage Isolation Isolation tested with 3 250 V DC...
BaseUnits for I/O modules 4.12 BU type C0, light-colored version, with AUX terminals, supply over supply terminals 4.12 BU type C0, light-colored version, with AUX terminals, supply over supply terminals Short designation Short designation: BU20-P6+A2+4D 4.12.1 Product overview Delivery options (packing unit VPE) 6ES7193-6BP20-0DC0 (VPE: 1 unit) View Figure 4-21...
Page 66
● Connection system in the form of push-in terminals You can find more information in the ET 200SP System Manual (https://support.industry.siemens.com/cs/ww/de/view/58649293). Maximum configuration per potential group The number of I/O modules that can be used per potential group depends on the following factors: 1.
Descriptions 1 to 6 Assignment is determined by the I/O module. You can find additional information in the I/O Module (http://support.automation.siemens.com/WW/view/en/55679691/133300) manual. 1 A, 2 A, AUX Protective conductor connection or voltage bus, freely usable up to 230 V AC/DC with max. 10 A. If you connect a voltage, it must belong to the same potential group as the rated supply voltage.
BaseUnits for I/O modules 4.12 BU type C0, light-colored version, with AUX terminals, supply over supply terminals 4.12.3 Technical specifications Technical specifications of the BU type C0, light-colored version, with AUX terminals, supply over supply terminals Article number 6ES7193-6BP20-0DC0 General information Product type designation Type C0 Supply voltage...
BaseUnits for I/O modules 4.13 BU type C1, dark-colored version, with AUX terminals, supply over P1, P2 busbar 4.13 BU type C1, dark-colored version, with AUX terminals, supply over P1, P2 busbar Short designation Short designation: BU20-P6+A2+4B 4.13.1 Product overview Delivery options (packing unit VPE) 6ES7193-6BP20-0BC1 (VPE: 1 unit) View...
● Two AUX terminals for connecting a PE terminal or potential. The AUX busbar is not connected to the I/O module. Max. 24 V DC/10 A ● Connection system in the form of push-in terminals Connection cross-sections are available in the ET 200SP System Manual (https://support.industry.siemens.com/cs/ww/de/view/58649293). 4.13.2 Connecting Pin assignment...
BaseUnits for I/O modules 4.13 BU type C1, dark-colored version, with AUX terminals, supply over P1, P2 busbar Block diagram ① Backplane bus ② Power module ③ Terminals with connection to the I/O module ④ System-integrated, self-assembling voltage buses P1, P2 with connection to the supply termi- nals (through the inserted I/O module) Connected to the adjacent module on the left ⑤...
Page 72
BaseUnits for I/O modules 4.13 BU type C1, dark-colored version, with AUX terminals, supply over P1, P2 busbar Article number 6ES7193-6BP20-0BC1 Potential separation between backplane bus and supply voltage between process terminals and supply voltage Isolation Isolation tested with 3 250 V DC Dimensions Width 20 mm...
BaseUnits for I/O modules 4.14 BU type D0, dark-colored version, without AUX terminals, supply over supply terminals 4.14 BU type D0, dark-colored version, without AUX terminals, supply over supply terminals Short designation Short designation: BU20-P12+A0+0B 4.14.1 Product overview Delivery options (packing unit VPE) 6ES7193-6BP00-0BD0 (VPE: 1 unit) View Figure 4-25...
● 12 terminals to the process (assignment with the I/O module) ● Connection system in the form of push-in terminals Connection cross-sections are available in the ET 200SP System Manual (https://support.industry.siemens.com/cs/ww/de/view/58649293). Note The shield connection (shield support and shield terminal) is not intended for BaseUnit BU20-P12+A0+0B and must not be installed.
BaseUnits for I/O modules 4.14 BU type D0, dark-colored version, without AUX terminals, supply over supply terminals Block diagram ① Backplane bus ② I/O module ③ Terminals with connection to the I/O module ④ System-integrated, self-assembling voltage buses P1, P2 without connection to the terminals, connected to the adjacent module on the left ⑤...
BaseUnits for I/O modules 4.15 BU type F0, dark-colored version, with AUX terminals, supply over supply terminals 4.15 BU type F0, dark-colored version, with AUX terminals, supply over supply terminals Short designation Short designation: BU20-P8+A4+0B 4.15.1 Product overview When you use the AUX terminals as a PE busbar: NOTICE When AUX is used as PE, AUX must be identified as green-yellow (e.g., gn/ye color-coded labels).
● Access to the AUX busbar via terminals 1 A to 4 A max. 24 V DC/10 A ● 8 terminals to the process (occupied by the I/O module) ● Connection system in the form of push-in terminals Connection cross-sections are available in the ET 200SP System Manual (https://support.industry.siemens.com/cs/ww/de/view/58649293). 4.15.2 Connecting up Pin assignment...
BaseUnits for I/O modules 4.15 BU type F0, dark-colored version, with AUX terminals, supply over supply terminals Block diagram ① Backplane bus ② I/O module ③ Terminals with connection to the I/O module ④ System-integrated, self-assembling voltage buses P1, P2 without connection to the terminals, connected to the adjacent module on the left ⑤...
Page 79
BaseUnits for I/O modules 4.15 BU type F0, dark-colored version, with AUX terminals, supply over supply terminals Article number 6ES7193-6BP20-0BF0 Potential separation between backplane bus and supply voltage between process terminals and supply voltage between power bus and supply voltage Isolation Isolation tested with 3 250 V DC/1 min (type test), 2 545 V DC/2 s...
BaseUnits for I/O modules 4.16 BU type U0, light-colored version without AUX terminals 4.16 BU type U0, light-colored version without AUX terminals Short designation Short designation: BU20-P16+A0+2D 4.16.1 Product overview Delivery options (packing unit VPE) 6ES7193-6BP00-0DU0 (VPE: 1 unit) 6ES7193-6BP00-2DU0 (VPE: 10 units) View Figure 4-29 BU type U0, light-colored version without AUX terminals...
● Connection system in the form of push-in terminals Connection cross-sections are available in the ET 200SP System Manual (https://support.industry.siemens.com/cs/ww/de/view/58649293). Maximum configuration per potential group The number of I/O modules that can be used per potential group depends on the following factors: 1.
BaseUnits for I/O modules 4.16 BU type U0, light-colored version without AUX terminals Block diagram ① Backplane bus ② I/O module ③ Terminals with connection to the I/O module ④ System-integrated, self-assembling voltage buses P1, P2 with connection to the supply termi- nals, interrupted to the adjacent module on the left (forms a new potential group) ⑤...
Page 83
BaseUnits for I/O modules 4.16 BU type U0, light-colored version without AUX terminals Article number 6ES7193-6BP00-0DU0 Mains filter integrated • Current carrying capacity up to 60 °C, max. 10 A For P1 and P2 bus, max. 10 A For AUX bus, max. 10 A For process terminals, max.
BaseUnits for I/O modules 4.17 BU type U0, dark-colored version, without AUX terminals 4.17 BU type U0, dark-colored version, without AUX terminals Short designation Short designation: BU20-P16+A0+2B 4.17.1 Product overview Delivery options (packing unit VPE) 6ES7193-6BP00-0BU0 (VPE: 1 unit) 6ES7193-6BP00-2BU0 (VPE: 10 units) View Figure 4-31 BU type U0, dark-colored version, without AUX terminals...
● No access to the AUX busbar via terminals ● 16 terminals to the process (assignment through the I/O module) ● Connection system in the form of push-in terminals Connection cross-sections are available in the ET 200SP System Manual (https://support.industry.siemens.com/cs/ww/de/view/58649293). 4.17.2 Connection Pin assignment...
BaseUnits for I/O modules 4.17 BU type U0, dark-colored version, without AUX terminals Block diagram ① Backplane bus ② I/O module ③ Terminals with connection to the I/O module ④ System-integrated, self-assembling voltage buses P1, P2 with connection to the supply termi- nals, connected to the adjacent module on the left ④...
Page 87
BaseUnits for I/O modules 4.17 BU type U0, dark-colored version, without AUX terminals Article number 6ES7193-6BP00-0BU0 Mains filter integrated • Current carrying capacity up to 60 °C, max. 10 A For P1 and P2 bus, max. 10 A For AUX bus, max. 10 A For process terminals, max.
The AUX1 bus is not supported in the BaseUnits of the SIMATIC ET 200SP motor starters. You can find assembly rules of the BaseUnits for the SIMATIC ET 200SP motor starter in the System Manual SIMATIC ET 200SP motor starters.
BaseUnits for motor starters 5.2 BU30-MS1 - BaseUnit with 24 V DC and 500 V AC infeed BU30-MS1 - BaseUnit with 24 V DC and 500 V AC infeed 5.2.1 Product overview Article number 3RK1908-0AP00-0AP0 View Figure 5-1 BaseUnit with 24 V DC and 500 V AC infeed BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 02/2018, A5E03727049-AJ...
1. Total current requirement of all motor starters operated on this infeed group. 2. Ambient temperature and installation type in which the motor starters are operated. You can find further information in the derating table in the Manual SIMATIC ET 200SP motor starters (https://support.industry.siemens.com/cs/ww/en/view/109479973).
Page 91
BaseUnits for motor starters 5.2 BU30-MS1 - BaseUnit with 24 V DC and 500 V AC infeed Block diagram The figure below shows the block diagram of the BaseUnit with 24 V DC and 500 V AC infeed. ① Backplane bus ②...
BaseUnits for motor starters 5.2 BU30-MS1 - BaseUnit with 24 V DC and 500 V AC infeed 5.2.3 Technical specifications Technical specifications of the BaseUnit with 24 V DC and 500 V AC infeed 3RK1908-0AP00-0AP0 Product type designation BU30-MS1 Galvanic isolation Galvanic isolation between backplane bus and supply voltage Insulation tested with...
BaseUnits for motor starters 5.3 BU30-MS2 - BaseUnit with 500 V AC infeed BU30-MS2 - BaseUnit with 500 V AC infeed 5.3.1 Product overview Article number 3RK1908-0AP00-0CP0 View Figure 5-3 BaseUnit with 500 V AC infeed BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 02/2018, A5E03727049-AJ...
1. Total current requirement of all motor starters operated on this infeed group. 2. Ambient temperature and installation type in which the motor starters are operated. You can find further information in the derating table in the Manual SIMATIC ET 200SP motor starters.
Page 95
BaseUnits for motor starters 5.3 BU30-MS2 - BaseUnit with 500 V AC infeed Block diagram The figure below shows the block diagram of the BaseUnit with 500 V AC infeed. ① Backplane bus ② Motor starter module ③ Connected power buses 24 V DC, M ④...
BaseUnits for motor starters 5.3 BU30-MS2 - BaseUnit with 500 V AC infeed 5.3.3 Technical specifications Technical specifications of the BaseUnit with 500 V AC infeed 3RK1908-0AP00-0CP0 Product type designation BU30-MS2 Galvanic isolation Galvanic isolation between backplane bus and supply voltage Insulation tested with 2500 V AC Rated operating voltage...
BaseUnits for motor starters 5.4 BU30-MS3 - BaseUnit with 24 V DC infeed BU30-MS3 - BaseUnit with 24 V DC infeed 5.4.1 Product overview Article number 3RK1908-0AP00-0BP0 View Figure 5-5 BaseUnit with 24 V DC infeed BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 02/2018, A5E03727049-AJ...
5.4 BU30-MS3 - BaseUnit with 24 V DC infeed Properties ● BaseUnit suitable for all fail-safe and non-fail-safe SIMATIC ET 200SP High Feature motor starters ● The BaseUnit opens a new potential group (24 V DC). The power buses P1 and P2 are interrupted to the left-hand neighboring module (BaseUnit, interface module/CPU).
Page 99
BaseUnits for motor starters 5.4 BU30-MS3 - BaseUnit with 24 V DC infeed Block diagram The figure below shows the three-phase connection with 24 V infeed and mains infeed. ① Backplane bus ② Motor starter module ③ Interrupted busbars 24 V DC, M ④...
BaseUnits for motor starters 5.4 BU30-MS3 - BaseUnit with 24 V DC infeed 5.4.3 Technical specifications Technical specifications of the BaseUnit with 24 V DC infeed 3RK1908-0AP00-0BP0 Product type designation BU30-MS3 Galvanic isolation Galvanic isolation between backplane bus and supply voltage Insulation tested with 2500 V AC Rated operating voltage...
BaseUnits for motor starters 5.5 BU30-MS4 - BaseUnit without infeed Properties ● BaseUnit suitable for all fail-safe and non-fail-safe SIMATIC ET 200SP High Feature motor starters ● No new potential groups are opened with this BaseUnit. ● The potential group (24 V DC) is looped through.
Page 103
BaseUnits for motor starters 5.5 BU30-MS4 - BaseUnit without infeed Block diagram The figure below shows the block diagram of the BaseUnit without infeed. ① Backplane bus ② Motor starter module ③ Connected busbars 24 V DC, M ④ Interrupted AUX bus ⑤...
BaseUnits for motor starters 5.5 BU30-MS4 - BaseUnit without infeed 5.5.3 Technical specifications Technical specifications of BaseUnit without infeed 3RK1908-0AP00-0DP0 Product type designation BU30-MS4 Galvanic isolation Galvanic isolation between backplane bus and supply voltage Insulation tested with 2500 V AC Rated operating voltage 24 V DC Max.
BaseUnits for motor starters 5.6 BU30-MS5 BaseUnit with 500 V AC infeed and F-DI BU30-MS5 BaseUnit with 500 V AC infeed and F-DI 5.6.1 Product overview Article number 3RK1908-0AP00-0EP0 View Figure 5-9 BaseUnit with 500 V AC and F-DI BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 02/2018, A5E03727049-AJ...
Page 106
5.6 BU30-MS5 BaseUnit with 500 V AC infeed and F-DI Properties ● BaseUnit suitable for all fail-safe SIMATIC ET 200SP High Feature motor starters ● The BaseUnit takes over the potential group (P1, P2) from the adjacent module on the left.
F-DI: Connection of fail-safe signal M: Reference potential of fail-safe signal L1(L), L2(N), L3, PE Power supply Assignment is determined by the motor starter. You can find more information in the ET 200SP Motor Starter (https://support.industry.siemens.com/cs/ww/en/view/109479973) manual. BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 02/2018, A5E03727049-AJ...
Page 108
BaseUnits for motor starters 5.6 BU30-MS5 BaseUnit with 500 V AC infeed and F-DI Block diagram The figure below shows the two-phase connection with 500 V AC infeed and F-DI: ① Backplane bus ② Motor starter module ③ Connected busbars 24 V DC, M ④...
BaseUnits for motor starters 5.6 BU30-MS5 BaseUnit with 500 V AC infeed and F-DI 5.6.3 Technical specifications Technical specifications of the BaseUnit with 500 V AC infeed and F-DI 3RK1908-0AP00-0EP0 Product type designation BU30-MS5 Galvanic isolation Galvanic isolation between backplane bus and supply voltage Insulation tested with 2500 V AC...
BaseUnits for motor starters 5.7 BU30-MS6 BaseUnit without infeed and with F-DI BU30-MS6 BaseUnit without infeed and with F-DI 5.7.1 Product overview Article number 3RK1908-0AP00-0FP0 View Figure 5-11 BaseUnit without 500 V AC infeed, with F-DI BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 02/2018, A5E03727049-AJ...
BaseUnits for motor starters 5.7 BU30-MS6 BaseUnit without infeed and with F-DI Properties ● BaseUnit suitable for all fail-safe SIMATIC ET 200SP High Feature motor starters ● The BaseUnit takes over the potential group (P1, P2) from the adjacent module on the left.
Page 112
BaseUnits for motor starters 5.7 BU30-MS6 BaseUnit without infeed and with F-DI Block diagram The following figure shows the block diagram for the BaseUnit without infeed, but with fail- safe input: ① Backplane bus ② Motor starter module ③ Connected busbars 24 V DC, M ④...
BaseUnits for motor starters 5.7 BU30-MS6 BaseUnit without infeed and with F-DI 5.7.3 Technical specifications Technical specifications of BaseUnit without infeed, with F-DI 3RK1908-0AP00-0FP0 Product type designation BU30-MS6 Galvanic isolation Galvanic isolation between backplane bus and supply voltage Insulation tested with 2500 V AC Rated operating voltage 24 V DC...
STEP 7 HSP0293 up to V5.5 SP4 Configurable as of version • You can find additional information on the use of the potential distributor modules in the ET 200SP Distributed I/O System (http://support.automation.siemens.com/WW/view/en/58649293) system manual. BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 02/2018, A5E03727049-AJ...
Potential distributor modules 6.2 PotDis-BU type P1, light-colored version PotDis-BU type P1, light-colored version 6.2.1 Short designation Short designation Light-colored version with 16 terminals to P1 + 2 supply terminals P1/P2. Short designation: PotDis-BU-P1/D-R. D stands for a new potential group, which means P1, P2, AUX separated to the left, R stands for red spring release.
Potential distributor modules 6.2 PotDis-BU type P1, light-colored version Properties ● BaseUnit suitable for all PotDis terminal blocks of the type "P1/P2/N0/P0". Can be recognized by the laser inscription on the front and/or the last two digits of the article number.
Potential distributor modules 6.2 PotDis-BU type P1, light-colored version Block diagram ① Backplane bus ② PotDis-TB terminal block ③ Terminals with connection to the supply voltage P1 ④ Disconnected voltage bus with connection to the terminals for supply ⑤ Interrupted AUX busbar Figure 6-2 Block diagram of the PotDis-BU type P1, light-colored version 6.2.4...
Page 118
Potential distributor modules 6.2 PotDis-BU type P1, light-colored version Article number 6ES7193-6UP00-0DP1 Potential separation between backplane bus and supply voltage Isolation Isolation tested with 3 250 V DC Ambient conditions Ambient temperature during operation 0 °C; No condensation horizontal installation, min. •...
Potential distributor modules 6.3 PotDis-BU type P1, dark-colored version PotDis-BU type P1, dark-colored version Short designation Dark-colored version with 16 terminals to P1 + 2 supply terminals P1/P2. Short designation: PotDis-BU-P1/B-R. B stands for bridged potential group, which means P1, P2, AUX bridged to the left, R stands for red spring release.
Potential distributor modules 6.3 PotDis-BU type P1, dark-colored version Properties ● BaseUnit suitable for all PotDis terminal blocks of the type "P1/P2/N0/P0". Can be recognized by the laser inscription on the front and/or the last two digits of the article number.
Potential distributor modules 6.3 PotDis-BU type P1, dark-colored version Block diagram ① Backplane bus ② PotDis-TB terminal block ③ Terminals with connection to the supply voltage P1 ④ Connected voltage bus with connection to the terminals ⑤ Connected AUX busbar Figure 6-4 Block diagram of the PotDis-BU type P1, dark-colored version 6.3.3...
Page 122
Potential distributor modules 6.3 PotDis-BU type P1, dark-colored version Article number 6ES7193-6UP00-0BP1 Hardware configuration Formation of potential groups New potential group • Potential group continued from the left • Potential separation between backplane bus and supply voltage Isolation Isolation tested with 3 250 V DC Ambient conditions Ambient temperature during operation...
Potential distributor modules 6.4 PotDis-BU type P2, light-colored version PotDis-BU type P2, light-colored version 6.4.1 Short designation Short designation Light-colored version with 16 terminals to P2 + 2 supply terminals P1/P2. Short designation: PotDis-BU-P2/D-B. D stands for a new potential group, which means P1, P2, AUX separated to the left, B stands for blue spring release.
Potential distributor modules 6.4 PotDis-BU type P2, light-colored version Properties ● BaseUnit suitable for all PotDis terminal blocks of the type "P1/P2/N0/P0". Can be recognized by the laser inscription on the front and/or the last two digits of the article number.
Potential distributor modules 6.4 PotDis-BU type P2, light-colored version Block diagram ① Backplane bus ② PotDis-TB terminal block ③ Terminals with connection to ground P2 ④ Disconnected voltage bus with connection to the terminals for supply ⑤ Interrupted AUX busbar Figure 6-6 Block diagram of the PotDis-BU type P2, light-colored version 6.4.4...
Page 126
Potential distributor modules 6.4 PotDis-BU type P2, light-colored version Article number 6ES7193-6UP00-0DP2 Hardware configuration Formation of potential groups New potential group • Potential group continued from the left • Potential separation between backplane bus and supply voltage Isolation Isolation tested with 3 250 V DC Ambient conditions Ambient temperature during operation...
Potential distributor modules 6.5 PotDis-BU type P2, dark-colored version PotDis-BU type P2, dark-colored version 6.5.1 Short designation Short designation Dark-colored version with 16 terminals to P2 + 2 supply terminals P1/P2. Short designation: PotDis-BU-P2/B-B. B stands for bridged potential group, which means P1, P2, AUX bridged to the left, B stands for blue spring release.
Potential distributor modules 6.5 PotDis-BU type P2, dark-colored version Properties ● BaseUnit suitable for all PotDis terminal blocks of the type "P1/P2/N0/P0". Can be recognized by the laser inscription on the front and/or the last two digits of the article number.
Potential distributor modules 6.5 PotDis-BU type P2, dark-colored version Block diagram ① Backplane bus ② PotDis-TB terminal block ③ Terminals with connection to ground P2 ④ Connected voltage bus with connection to the terminals ⑤ Connected AUX busbar Figure 6-8 Block diagram of the PotDis-BU type P2, dark-colored version 6.5.4 Technical specifications...
Page 130
Potential distributor modules 6.5 PotDis-BU type P2, dark-colored version Article number 6ES7193-6UP00-0BP2 Hardware configuration Formation of potential groups New potential group • Potential group continued from the left • Potential separation between backplane bus and supply voltage Isolation Isolation tested with 3 250 V DC Ambient conditions Ambient temperature during operation...
Page 132
Potential distributor modules 6.6 PotDis-TB Properties ● Terminal blocks matching all BaseUnits PotDis-BU – Current carrying capacity per terminal: Max. 10 A ● 18 terminals – PotDis-TB-P1-R terminal block: Red terminals with connection to the supply voltage P1 of the BaseUnit PotDis-BU –...
Potential distributor modules 6.6 PotDis-TB 6.6.2 Connecting Pin assignment Pin assignment for PotDis-TB terminal block Terminal block Terminal Explanation PotDis-TB-P1-R Rated supply voltage up to 48 V DC with max. 10 A (18 red terminals) PotDis-TB-P2-B Ground (18 blue terminals) PotDis-TB-n.c.-G n c.
Potential distributor modules 6.6 PotDis-TB 6.6.3 Technical specifications Technical specifications of the PotDis-TB-P1_R terminal block Article number 6ES7193-6TP00-0TP1 General information Product type designation PotDis TB P1-R, PU 1 Supply voltage Rated value (DC) 48 V; max. For P1 and P2 bus •...
Page 135
Potential distributor modules 6.6 PotDis-TB Article number 6ES7193-6TP00-0TP1 Accessories Color coding labels CC12 for process terminals • Connection method Terminals Push-in terminal Terminal type • 0.14 mm²; 0.2 mm² without wire end ferrule Conductor cross-section, min. • 2.5 mm²; 1.5 mm² with wire end ferrule Conductor cross-section, max.
Page 136
Potential distributor modules 6.6 PotDis-TB Technical specifications of the PotDis-TB-P2-B terminal block Article number 6ES7193-6TP00-0TP2 General information Product type designation PotDis TB P2-B, PU 1 Supply voltage Rated value (DC) 48 V; max. For P1 and P2 bus • 48 V; max. for process terminals •...
Page 137
Potential distributor modules 6.6 PotDis-TB Article number 6ES7193-6TP00-0TP2 Accessories Color coding labels CC13 for process terminals • Connection method Terminals Push-in terminal Terminal type • 0.14 mm²; 0.2 mm² without wire end ferrule Conductor cross-section, min. • 2.5 mm²; 1.5 mm² with wire end ferrule Conductor cross-section, max.
Page 138
Potential distributor modules 6.6 PotDis-TB Technical specifications of the PotDis-TB-n.c.-G Article number 6ES7193-6TP00-0TN0 General information Product type designation PotDis TB n.c. G, PU 1 Supply voltage Rated value (DC) 48 V; max. for process terminals • Rated value (AC) 240 V; max. for process terminals •...
Page 139
Potential distributor modules 6.6 PotDis-TB Article number 6ES7193-6TP00-0TN0 Accessories Color coding labels CC10 for process terminals • Connection method Terminals Push-in terminal Terminal type • 0.14 mm²; 0.2 mm² without wire end ferrule Conductor cross-section, min. • 2.5 mm²; 1.5 mm² with wire end ferrule Conductor cross-section, max.
Page 140
Potential distributor modules 6.6 PotDis-TB Technical specifications of the PotDis-TB-BR-W terminal block Article number 6ES7193-6TP00-0TP0 General information Product type designation PotDis TB BR-W, PU 1 Supply voltage Rated value (DC) 48 V; max. for process terminals • Rated value (AC) 240 V;...
Page 141
Potential distributor modules 6.6 PotDis-TB Article number 6ES7193-6TP00-0TP0 Accessories Color coding labels CC10 for process terminals • Connection method Terminals Push-in terminal Terminal type • 0.14 mm²; 0.2 mm² without wire end ferrule Conductor cross-section, min. • 2.5 mm²; 1.5 mm² with wire end ferrule Conductor cross-section, max.
Dimension drawings of I/O modules Dimension drawing BU15-P16+A10+2D, BU15-P16+A10+2B, BU15-P16+A0+12D/T, BU15-P16+A0+12B/T The figure below shows the dimension drawing of the BU15-P16+A10+2D with plugged-in I/O module as an example. Figure A-1 Dimension drawing BU15-P16+A10+2D BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 02/2018, A5E03727049-AJ...
Page 143
Dimension drawings of I/O modules Dimension drawing BU15-P16+A0+2D, BU15-P16+A0+2B, BU15-P16+A0+2D/T, BU15-P16+A0+2B/T The figure below shows the dimension drawing of the BU15-P16+A0+2D with plugged-in I/O module as an example. Figure A-2 Dimension drawing BU15-P16+A0+2D BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 02/2018, A5E03727049-AJ...
Page 144
Dimension drawings of I/O modules Dimension drawing BU20-P6+A2+4D, BU20-P6+A2+4B, BU20-P12+A4+0B, BU20-P12+A0+0B, BU20-P12+A0+4B, BU20-P8+A4+0B The figure below shows the dimension drawing of the BU20-P12+A4+0B with plugged-in I/O module as an example. Figure A-3 Dimension drawing BU20-P12+A4+0B Dimension drawing test probe for measurement tap The figure below shows the dimension drawing of a suitable test probe for measurement tap at the BaseUnit.
Dimension drawings of motor starters Dimension drawing BU30-MS1, BU30-MS2, BU30-MS3, BU30-MS4, BU30-MS5, BU30-MS6 The figure below shows the dimension drawing of the BU30-MS-1 with plugged-in motor starter module as an example. Figure B-1 Dimension drawing BU30-MS1 BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 02/2018, A5E03727049-AJ...
Dimension drawings of the potential distributor modules Dimension drawing The figure below shows the dimension drawing of the PotDis-BU-P1/B-R with plugged-in PotDis-TB-P1-R terminal block. Figure 7-1 Dimension drawing of PotDis BU-P1/B-R with plugged-in terminal block BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 02/2018, A5E03727049-AJ...