Control Wiring - YASKAWA E7 Installation Manual

Ig.e7.03
Hide thumbs Also See for E7:
Table of Contents

Advertisement

Control Wiring

Control Circuit Wire Sizes
The auto mode speed reference (speed command) field wiring connection is made to E7 Drive terminals A1 or A2 (signal
positive), AC (signal common) and G (shield). Keep this lead length as short as possible to maintain signal quality. Insulated
twisted shielded pair wire (2 conductor # 18 ga, Belden 8760 or equivalent) is required. Do not run these wires in the same
conduit as other AC power or control wires. The shield must be connected on this end only, stub and isolate the other end. The
A2 signal employed is 4 to 20 mA with parameter H3-08 set for "2: 4 - 20 mA". For 0 to 10 VDC, parameter H3-08 is set for
"0: 0 - 10 VDC" and the E7 control board DIP switch S1-2 must be in the OFF position. (See Fig 2.4).
For remote operation, keep the length of the control wiring to 50m or less. Separate the control wiring from high-power lines
(input power, motor leads or relay sequence circuits) to reduce noise induction from peripheral devices.
When setting speed commands (frequency references) from an external speed potentiometer (and not from the Digital Opera-
tor), use shielded twisted-pair wires and ground the shield to terminal E(G), as shown in Fig 2.3. Terminal numbers and wire
sizes are shown in Table 2.7.
External
External
Frequency
Frequency
Reference
R eference
4 to 20m A
4 to 20m A
(P=Pair)
Terminals
S1, S2, S3, S4, S5, S6, S7
SN, SC, SP, +V, A1, A2,
AC, MI, M2, M3, M4,
MA, MB, MC, FM, AC,
AM, R+, R-, S+, S-, IG
E(G)
*1.
Use shielded twisted-pair cables to input an external speed command.
*2.
Yaskawa recommends using straight solderless terminals on digital inputs to simplify wiring and improve reliability.
*3.
Yaskawa recommends using a thin-slot screwdriver with a 3.5 mm blade width.
E (G)
E( G )
+V +15VDC, 20mA
+V +15V D C , 20m A
2k Ω
Ω
2k
A1 0-10VDC (20k Ω)
A 1 0-10V D C (20K
A2 H3-08
A 2 H 3-08
4-20m A (250K Ω)
4-20m A (250K
P
P
[0 to +10V (20K Ω)]
P
P
[0 to +10V (20K
AC
A C
Fig 2.3 Analog Input Terminal Configuration
Table 2.7 Terminal Numbers and Wire Sizes (Same for all Drives)
Tightening
Terminal
Torque
Screws
lb-in
(N•m)
Phoenix
4.2 to 5.3
*3
(0.5 to 0.6)
type
7.0 to 8.8
M3.5
(0.8 to 1.0)
Electrical Installation 2 - 12
E7
Ω
)
Ω
)
Ω
) ]
Possible
Recommended
Wire Sizes
Wire Size AWG
2
2
AWG (mm
)
(mm
Stranded
wire:
18
26 to 16
(0.75)
(0.14 to 1.5)
20 to 14
12
*2
(1.25)
(0.5 to 2
)
Signal
Terminal Connections
0-10Vdc
A1 to AC
4-20mA
A2 to AC
or
0-10Vdc
Wire Type
)
• Shielded, twisted-pair wire
• Shielded, polyethylene-covered,
vinyl sheath cable
*1

Advertisement

Table of Contents
loading

Table of Contents