To remove the circuit breaker from the structure,
reverse the procedure just described by turning the lev-
ering-in crank in a counterclockwise direction. Keep in
mind that safety interlocks may cause the circuit breaker
to open and/or springs to discharge during the removal
process. It depends on what condition the circuit break-
er was in as removal began.
For additional information on the levering mechanism,
refer to paragraph 5-6 in this manual.

4-8.2 OPERATION CHECK PERFORMANCE

Move the circuit breaker to the TEST position and
engage the secondary contacts following the procedure
described in paragraph 4-8.1. As soon as the closing
springs are charged, the condition will be indicated by a
Spring Charged/Discharged Indicator on the front of the
circuit breaker (Figure 3-5). In addition, the status of the
main contacts, open or closed, is indicated on the front
of the circuit breaker.
Close and trip the circuit breaker several times to verify
closing and tripping operations. Conclude by closing the
circuit breaker. The circuit breaker is now closed in the
TEST position with springs charged.
Figure 4-4 Typical VCP-W Circuit Breaker Bottom View
Effective 12/02
Figure 4-3 Engaging Extension Rails in a Lower Circuit
Breaker Compartment
Page 19
Ground Contact
Secondary Disconnect
Close Floor Tripper
Levering Latch
Trip Floor Tripper
Code Plates
MOC Operator
TOC Operator