I.B. 32-255-1G
Figure 6-15 Move Marker 15
Figure 6-16 Remove Marked Masking Tape from Cam
Figure 6-17 Place Tape on Right Side Panel of
Breaker
Step 10 - Remove the marker from hole "C".
Step 11 - Push the "push to open" clapper to open the
circuit breaker.
Effective 12/02
o
to Left
*Figure not to scale
*Note: Use the center of
the marker diameter to
determine "X" distance
"X" Inches
CloSure
Overtravel
TM
CloSure
Distance
TM
CloSure
Position
TM
Figure 6-18 Illustrative Testing Tape Sample
Step 12 - Inspect the circuit breaker to assure it is in the
open position and the closing springs are discharged.
Remove the transparent CloSure
tape from the cam and stick the tape on the front right
side sheet of the circuit breaker. Record the date of the
test and the operations counter reading on the tape
(Figures 6-16 and 6-17 and 6-18).
A-1
A-2
C-2
A-3
C-1 C-3
A-4
B-1
B-2
Figure 6-19 Front View of CloSure
Mounting/Testing Hole Locations (6352C49H01)
A
B
C
TM
Tool. Remove the
C-4 C-5
C-6
TM
Tool Showing
Page 41
8.0 to 10
Inches