Eaton 50VCPW-ND250 Installation, Operation And Maintenance Manual page 52

Vacuum circuit breake vcp-w series; vcpw-se series; vcpw-nd series
Table of Contents

Advertisement

Page 44
6-11 TROUBLESHOOTING CHART (Continued Next Page)
SYMPTOM
Fails To Close
Undesirably Closes
Fails To Trip
• No Trip Sound
INSPECTION AREA
• Closing Sound
but no close
• Control Circuit
• Mechanism
• Control Circuit
• Trip Mechanism
I.B. 32-255-1G
PROBABLE DEFECTS
• Pole Shaft
(Not open fully)
• Trip Latch Reset Spring
(Damaged or Missing)
• Trip Bar-D Shaft
(Fails to remain reset)
• Trip Latch-Hatchet
(Fails to remain reset)
• Trip Floor Tripper
(Fails to remain reset)
• Close Latch
(Binding)
• Close Latch Roller
(Binding)
• Trip Circuit Energized
• Close Circuit
(CS/C Getting Shorted)
• Close Release Latch
(Fails to reset)
• Close Floor Tripper
(Fails to reset)
• Control Power
(Fuse blown or switch off)
• Secondary Disconnect
• Auxiliary Switch
(a contact not making, poor or burned)
• Trip Coil
(Burned or open)
• Terminals and Connections
(Poor or burned or open)
• Trip Clapper
(Jammed)
Effective 12/02