Setting the serial port timeout value:
The Set Port Timeout All command sets the serial port inactivity timeout period. The timeout period defines the
maximum period of inactivity before automatically closing the Pass-Thru session.
The valid range for the timeout is 0 to 60 (in minutes). The default timeout is 5 minutes. The command can be used to
set individual ports (by ID or name) or set all ports.
NOTES:
 Setting the timeout value to "0" disables the timer.
 Only a numeric value is accepted.
To set the serial port timeout value for an individual port:
At the Switched -48 VDC: prompt, type set port timeout, followed by the port ID or name, followed by a timeout
value from 0 to 60 (in minutes), and press Enter.
To set the serial port timeout value for all ports:
At the Switched -48 VDC: prompt, type set port timeout all, followed by a timeout value from 0 to 60 (in minutes),
and press Enter.
Enabling or disabling the Serial Command Protocol (SCP) emulation:
This option notifies SCP of an MRV device on a specific serial port.
To enable or disable the SCP emulation:
At the Switched -48 VDC: prompt, type set port scp, followed by emulate, followed by none or MRV, and press
Enter.
Enabling or disabling the RFTAG option:
This option makes RF Code sensor tags available for the Server Technology wireless monitoring solution.
To enable or disable the RF Code sensor options:
At the Switched -48 VDC: prompt, type set port rftag, follow by the serial port name, followed by enabled or
disabled, and press Enter.
Displaying serial port information:
The Show Ports command displays information about all serial ports. This information includes:
Serial port data rate
Descriptive port name, if applicable
DSR signal checking settings
To display serial port information:
At the Switched -48 VDC: prompt, type show ports and press Enter.
Example
The following command displays all serial port information:
Switched -48 VDC: show ports<Enter>
Serial Port Configuration
Port ID: Console
DSR Check:
Data Rate: 9600
Command successful
84  Operations
Installation and Operations Manual
Port Name: CONSOLE
ON
CLI: Enabled
Connection Timeout: 10 minutes
SCP: Disabled
RFTAG: Enabled
-48 VDC Remote Power Manager