Enabling/disabling UPS voltage polling:
With a UPS record configured, the CDU by default enables voltage polling of the UPS. This feature can be enabled or
disabled using the Set UPS VPoll command.
To enable/ disable UPS voltage polling:
At the Switched -48 VDC: prompt, type set ups vpoll and press Enter.
At the prompt, enter the index number for the UPS record to be changed and press Enter.
At the prompt, type on or off, and press Enter.
Example
The following command disables voltage polling for the record at index number 2:
Switched -48 VDC: set ups vpoll<Enter>
UPS
UPS
Index
Type
1
Liebert
2
MGE
Select UPS (1-11): 2<Enter>
Voltage Polling: Off<Enter>
Adding an infeed to a UPS:
The Set UPS AddInfeed command adds a logical association of an infeed to a UPS.
To add an infeed to a UPS:
At the Switched -48 VDC: prompt, type set ups addinfeed and press Enter.
At the prompt, enter the index number for the UPS record to be changed and press Enter.
At the prompt, type the absolute infeed ID of the desired infeed, and press Enter.
Example
The following command associates infeed .aa to UPS record at index number 1:
Switched -48 VDC: set ups addinfeed<Enter>
UPS
UPS
Index
Type
1
APC
2
Liebert
Select UPS (1-11): 1<Enter>
Infeed ID: .aa<Enter>
Removing an infeed from a UPS:
The Set UPS DelInfeed command removes a logical association of an infeed from a UPS.
To remove an infeed from a UPS:
At the Switched -48 VDC: prompt, type set ups delinfeed and press Enter.
At the prompt, enter the index number for the UPS record to be changed and press Enter.
At the prompt, type the absolute infeed ID of the desired infeed, and press Enter.
Example
The following command removes the association of infeed .aa from UPS record at index number 2:
Switched -48 VDC: set ups addinfeed<Enter>
UPS
UPS
Index
Type
1
APC
2
Liebert
Select UPS (1-11): 2<Enter>
Infeed ID: .aa<Enter>
102  Operations
Installation and Operations Manual
Voltage
Polling
On
On
Infeed
IDs
.AA
Infeed
IDs
.AA
.AA