Power Monitoring; Outlets - Server Technology 4805-XLS-16B Installation And Operation Manual

48 vdc remote power manager
Table of Contents

Advertisement

Outlet State/Control State Field Values
Outlet State
Control State
On
On
Off
Off
Off
Pend On
Off
Reboot
On
Idle On
Off
Idle Off
On
Wake On
Off
Wake Off
On/Wait
Off
Off/Wait
On
On/Error
(varies)
Off/Error
(varies)
Off/Fuse
On
No Comm
(varies)

Power Monitoring

Outlets

The Power Monitoring > Outlets page displays outlets by absolute/descriptive names and shows outlet status and
outlet load.
NOTE: For DC products, only the outlet current measurement (in amps) is provided for outlet monitoring.
Monitor pages (like the Outlets page) refresh occasionally to reflect current status of the unit.
32  Operations
Installation and Operations Manual
Description
Outlet is on
Outlet is off
Outlet is off and about to turn on in response to a sequence timer
Outlet is off and a Reboot action has been initiated
A restart has occurred – Last Control State has been maintained
A restart has occurred – Last Control State has been maintained
A power-loss has occurred – Wakeup State has been applied
A power-loss has occurred – Wakeup State has been applied
Outlet state in transition – Another query of outlet status is required
Outlet state in transition – Another query of outlet status is required
Error State – Outlet should be off, but current is sensed at the outlet
Error State – Outlet should be on, but no current is sensed at the outlet
Outlet should be on, but a blown fuse has been detected
Communication to the outlet has been lost (control state will be applied when communication is
re-established)
-48 VDC Remote Power Manager