Changing the UPS host address:
The Set UPS Host command changes the IP address or hostname for each UPS record. Hostnames can be up to 60
characters long.
To change a UPS host address:
At the Switched -48 VDC: prompt, type set ups host and press Enter.
At the prompt, type the index number for the UPS record to be changed and press Enter.
At the prompt, type IP address or hostname for the UPS and press Enter.
Example
The following command changes UPS hostname for the record at index number 2 to 'DC1Liebert1':
Switched -48 VDC: set ups host<Enter>
1
Type:
Host/IP: DC1APC
2
Type:
Host/IP: DC1Liebert
Select UPS (1-11): 2<Enter>
Host/IP: DC1Liebert1<Enter>
Changing the UPS SNMP port:
With a UPS record configured, the CDU sends data requests to the default UPS SNMP port number 161. You can
change this port number using the Set UPS Port command.
To change the UPS SNMP port:
At the Switched -48 VDC: prompt, type set ups port and press Enter.
At the prompt, type the index number for the UPS record to be changed and press Enter.
At the prompt, type the desired port number and press Enter.
Example
The following command changes port for the UPS record at index number 1 to '162':
Switched -48 VDC: set ups port<Enter>
UPS
UPS
Index
Type
1
APC
2
Liebert
Select UPS (1-11): 1<Enter>
Port: 162<Enter>
Changing the UPS SNMP Get community string:
With a UPS record configured, the CDI sends data requests to the UPS using the default Get community string of
'public'. You can change this string using the Set UPS Commstr command.
 NOTE: The Get community string configured on the CDU must match the read-only community string configured on the UPS.
To change a UPS SNMP community string record:
At the Switched -48 VDC: prompt, type set ups commstr and press Enter.
At the prompt, type the index number for the UPS record to be changed and press Enter.
At the prompt, type the Get community string for the UPS and press Enter.
Example
The following command changes Get community string for the record at index number 2 to 'readonly':
Switched -48 VDC: set ups commstr<Enter>
UPS
UPS
Index
Type
1
APC
2
Liebert
Select UPS (1-11): 2<Enter>
Community String: readonly<Enter>
-48 VDC Remote Power Manager
Installation and Operations Manual
APC
Liebert
Port
161
161
Community
String
public
public
Operations  101