Server Technology 4805-XLS-16B Installation And Operation Manual page 54

48 vdc remote power manager
Table of Contents

Advertisement

Enabling or disabling Environmental Monitor traps:
Click on the Environmental Monitor Traps link.
On the subsequent page, select or deselect the desired traps and click Apply.
Configuring Temperature and Relative Humidity sensor traps:
Click the Sensor Traps and Thresholds link.
On the subsequent Sensor Traps and Thresholds page, select or deselect the desired trap checkboxes and click Apply.
Configuring Temperature and Relative Humidity sensor thresholds:
Click the Sensor Traps and Thresholds link.
For temperature thresholds, type a low and high temperature value in the Low Temp and High temp fields and click
Apply.
For relative humidity thresholds, type a low and high humidity percentage in the Low Humid and High Humid fields,
and click Apply.
NOTE: For temperature thresholds, the valid range is 0 to 123 in degrees Celsius or 32 to 254 in degrees Fahrenheit. For relative humidity,
the valid range is 0 to 100 (in percentage of relative humidity).
Configuring Temperature Recovery Delta:
Click the Sensor Traps and Thresholds link.
The Recovery Delta field allows configuration of the number of degrees of change needed to recover from a
temperature alarm. After exceeding the high-temperature threshold, the temperature value must fall below the high-
temperature threshold by the number of degrees specified in the Recovery Delta field before the sensor recovers.
For example, if the High Temp value is 80 degrees Fahrenheit, and the Recovery Delta field is 2 degrees Fahrenheit,
the sensor will not recover until a temperature value of 78 degrees Fahrenheit is reported.
To configure a temperature recovery delta, type a value (in degrees) in the Recovery Delta field and click Apply.
NOTE: The acceptable value range for the Recovery Delta field is 0-10 degrees for Celsius and 0-18 degrees for Fahrenheit. The default
value for the Recovery Delta field is 1 degree Celsius and 2 degrees Fahrenheit.
54  Operations
-48 VDC Remote Power Manager
Installation and Operations Manual

Advertisement

Table of Contents
loading

Table of Contents