Table A-3. Range and Sensor Limits
Rosemount 3051CA
Minimum
Range
span
0.3 psia
1
(20,6 mbar)
1.5 psia
2
(0,103 bar)
8 psia
3
(0,55 bar)
40 psia
4
(2,76 bar)
1.
Assumes atmospheric pressure of 14.7 psig.
A.2.2 Zero and span adjustment
requirements (HART and Low
Power)
Zero and span values can be set anywhere within the range
limits stated in
Table A-1, Table A-2,
Span must be greater than or equal to the minimum span
stated in
Table A-1, Table A-2,
A.2.3 Service
Liquid, gas, and vapor applications
A.2.4 4–20 mA (output code A)
Output
Two-wire 4–20 mA, user-selectable for linear or square root
output. Digital process variable superimposed on 4–20 mA
signal, available to any host that conforms to the HART
protocol.
Power supply
External power supply required. Standard transmitter
(4–20 mA) operates on 10.5 to 55 Vdc with no load.
Specifications and Reference Data
Range and sensor limits
Upper
Lower
(URL)
(LRL)
30 psia
0 psia
(2,07 bar)
(0 bar)
150 psia
0 psia
(10,3 bar)
(0 bar)
800 psia
0 psia
(55,2 bar)
(0 bar)
4000 psia
0 psia
(275,8 bar)
(0 bar)
and
Table
A-3.
and
Table
A-3.
Specifications and Reference Data
Rosemount 3051T
Range and sensor limits
Minimum
Range
span
0.3 psi
1
(20,6 mbar)
(2,07 bar)
1.5 psi
2
(0,103 bar)
(10,3 bar)
8 psi
3
(0,55 bar)
(55,2 bar)
40 psi
4
(2,76 bar)
(275,8 bar)
2000 psi
10000 psi
5
(137,9 bar)
(689,4 bar)
Load limitations
Maximum loop resistance is determined by the voltage level
of the external power supply, as described by:
Max. Loop Resistance = 43.5 (Power Supply Voltage – 10.5)
Voltage (Vdc)
Communication requires a minimum
loop resistance of 250 ohms.
1. For CSA approval, power supply must not exceed 42.4 V.
A.2.5 F
OUNDATION
code F) and PROFIBUS

(output code W)

Power supply
External power supply required; transmitters operate on
9.0–32.0 Vdc transmitter terminal voltage.
Upper
Lower
(URL)
(LRL)
30 psi
0 psia
(0 bar)
150 psi
0 psia
(0 bar)
800 psi
0 psia
(0 bar)
4000 psi
0 psia
(0 bar)
0 psia
(0 bar)
O
p
Fieldbus (output
®
May 2017
(1)
Lower
(LRL)
(Gage)
–14.7 psig
(–1,01 bar)
–14.7 psig
(–1,01 bar)
–14.7 psig
(–1,01 bar)
–14.7 psig
(–1,01 bar)
–14.7 psig
(–1,01 bar)
94