Write Protect - Emerson Rosemount 3051 Reference Manual

Pressure transmitter with hart protocol
Hide thumbs Also See for Rosemount 3051:
Table of Contents

Advertisement

Reference Manual
00809-0100-4001, Rev KA

Write Protect

This message appears if you attempt to change the transmitter configuration data while the security
jumper is in the ON position. See
security jumper.
Field Communicator diagnostics
Table 5-2
descriptions.
Variable parameters within the text of a message are indicated with <variable parameter>.
Reference to the name of another message is identified by [another message].
Table 5-2. Field Communicator Messages
Message
1k snsr EEPROM
error-factory ON
1k snsr EEPROM
error-user-no out ON
1k snsr EEPROM
error-user ON
4k micro EEPROM
error-factory ON
4k micro EEPROM
error-user-no out ON
4k micro EEPROM
error-user ON
4k snsr EEPROM
error-factory ON
4k snsr EEPROM
error-user ON
Add item for ALL device types or
only for this ONE device type.
Command Not Implemented
Communication Error
Configuration memory not
compatible with connected device
CPU board not initialized ON
CPU EEPROM write failure ON
Device Busy
Troubleshooting
"Security (write protect)" on page 44
is a list of messages used by the Field Communicator (HC) and their corresponding
Description
Replace the transmitter
Use the Field Communicator to reset the following parameters: remote
seal isolator, remote seal fill fluid, flange material, o-ring material,
transmitter type, remote seal type, flange type, meter type, number of
remote seals.
Perform a full trim to recalibrate the transmitter.
Replace the electronics board.
Use the Field Communicator to reset the message field.
Use the Field Communicator to reset the following parameters: units,
range values, damping, analog output, transfer function, tag, scaled
meter values. Perform a D/A trim to ensure that the error is corrected.
Replace the transmitter.
Use the Field Communicator to reset the temperature units and the
calibration type.
Asks the user whether the hot key item being added should be added for
all device types or only for the type of device that is connected.
The connected device does not support this function.
The communicator and the device are not communicating correctly.
Check all connections between the Field Communicator and the device
and resend the information.
The configuration stored in memory is incompatible with the device to
which a transfer has been requested.
The electronics board is not initialized.
Replace the electronics board.
Message sent to electronics board from HART
electronics board.
The connected device is busy performing another task.
Troubleshooting
May 2017
for more information about the
®
signal failed. Replace the
81