APPENDIX

APPENDIX
Appendix 1 Differences between AJ71PB92D/A1SJ71PB92D Software
Versions

Appendix 1.1 Differences between A1SJ71PB92D Software Versions

(1) The extended service mode and slave station status indication area were added to the
software version E.
Buffer Memory
Address: 0 to 959
Address: 960 to
1919
Address: 2112 to
2116
Address: 2128 to
2247
(Extended service
mode only)
As the software version E or later uses the extended service mode, the new setting position "No.
E" was added to the MODE setting switch.
If the MODE setting switch on the A1SJ71PB92D of the software version D or earlier is set to No.
E, we cannot guarantee its operation. Do not set the MODE setting switch of the software version
D or earlier to No. E.
(2) The operation mode changing function and MELSEC ProfiMap's remote parameter function
were added to the software version G.
Buffer Memory
Address: 2254
Address: 2255
Address: 2256
• Input area
Normal service mode: 32 bytes, fixed length
Extended service mode: 244 bytes, variable length
• Output area
Normal service mode: 32 bytes, fixed length
Extended service mode: 244 bytes, variable length
• Slave status area
(The status of each slave station is indicated.)
• I/O start address area
(The I/O area starting address of each slave station is
indicated.)
• Current operation mode
(The current operation mode is indicated.)
• Operation mode change request area
(Set the required operation mode.)
• Operation mode change result area
(The operation mode change request result is indicated.)
I/O Signal
• Operation mode signal
X10
• Operation mode change completion signal
X11
• Operation mode change request signal
Y11
MLESEC
ProfiMap
Remote
• Can be set.
parameter
function
Software Version E or Later
Software Version G or Later
Software Version G or Later
Software Version G or Later
A-1
MELSEC-A
Software Version D or
Earlier
• Input area
• Normal service mode: 32
bytes, fixed length
• Output area
• Normal service mode: 32
bytes, fixed length
• Not usable
• Not usable
Software Version F or
Earlier
• Not usable
• Not usable
• Not usable
Software Version F or
Earlier
• Not usable
• Not usable
• Not usable
Software Version F or
Earlier
• Cannot be set.