3. SPECIFICATIONS
3.2

Performance Specifications

Item
Model
Electrical standards and characteristics
Medium
Network configuration
Data link method
Transmission encoding method
Transmission speed/maximum
transmission distance *1 *2
Maximum number of repeaters/network
Maximum number of stations/segment
Maximum number of slave stations/master
station
Number of connection nodes (number of
repeaters)
Transmittable data
Number of occupied I/O
5VDC Internal current consumption
Noise durability, dielectric withstand voltage
insulation resistor
External dimensions
Weight
*1 Transmission speed control within +/- 0.3% (PROFIBUS part 1)
*2 Distance that the transmission distance can be expanded by (m/network) using repeaters
Maximum transmission distance (m/network) = (number of repeaters + 1) × transmission distance (m/segment)
*3 The *3 restriction will cease to exist when the system is configured exclusively by the master and slave stations of
the hardware version B or later versions.
Point
*3 When using 12Mbps transmission speed, restriction of the cable length and the number of connector stations
described below is necessary.
1) Minimum length of the cable between stations is greater than or equal to one meter.
2) Maximum number of the connection stations are smaller than or equal to 11.
Master
1)
AJ71PB92D
Complies with EIA-RS485
Shielded twisted cable
Bus (however, tree type when a repeater is used)
• Token passing method (master side)
• Polling method (master/slave side)
NRZ
Transmission speed Transmission distance [m/segment]
9.6 [kbps]
19.2 [kbps]
93.75 [kbps]
187.5 [kbps]
500 [kbps]
1.5 [Mbps]
3 [Mbps]
6 [Mbps]
12 [Mbps]
3 units *2
32 stations *3 (See "Point")
60 slaves
32, 62 (1), 92 (2), 126 (3)
32 bytes/1 station (Normal service mode)
244 bytes/1 station (Extemded service mode)
32 points (I/O allocation : special 32 points)
0.54 A
Depending on the AJ71PB92D/A1SJ71PB92D installation system power supply module
specifications. (refer to the CPU Module User's Manual.)
250 mm (9.84 in.)(H) × 37.5 mm (1.48 in.)(W)
× 106 mm (4.17 in.)(D)
0.37 kg
Slave
Slave
1)
3-2
Specifications
1200
1000
400
200
100
100 *3
130 mm (5.12 in.)(H) × 34.5 mm (1.36 in.)(W)
× 93.6 mm (3.69 in.)(D)
2)
Slave
MELSEC-A
A1SJ71PB92D
Maximum transmission distance
when 3 repeaters are used
[m/network]
4800
4000
1600
800
400
0.56 A
0.27 kg
Slave
1)