Layout Of Electrical Terminals - Sanyo SPW-CR1503GDYH8 Technical Data & Service Manual

W-eco multi system series
Table of Contents

Advertisement

2. Optional Controller (system controller)

7 Layout of electrical terminals

3
NOTE
1) *1: All air conditioners turn on at same mode and operation conditions of when it stops as before.
2) *2: The output signal will appear when any one of indoor units turns on.
3) *3: The alarm signal will appear when any one of indoor units has a trouble.
Ground for
power wiring
L (L1)
N (L2)
B3 B2 B1 A3 A2 A1
How to connect electrical wiring
1) Basic wiring
L (L1):
N (L2):
C1:
C2:
C3:
Auxiliary
C4:
Ground for inter-unit control wiring
2) Terminals for remote monitoring
A1:
Input for turning on air conditioners concurrently. (*1)
A2:
Input for turning off air conditioners concurrently.
A3:
Common input for turning air conditioners on or off.
B1:
On operation state indicator output. (*2)
B2:
Alarm indicator output. (*3)
B3:
Common indicator output.
Control of W-ECO MULTI SYSTEM
Clamp for electrical wiring
CN02
C1
C2
C3
C4
Power supply (
50 Hz / 60 Hz, 220 - 240 V)
Inter-unit control wiring. (Low voltage)
III - 40
Connector (CN02)
for weekly timer
(TM-WBGN: optional)
P.C board
1789_M_I
DC24V
potential free contact
DC24V, Max 1A
TD831077