Sanyo SPW-CR1503GDYH8 Technical Data & Service Manual page 29

W-eco multi system series
Table of Contents

Advertisement

1. Model Selecting and Capacity Calculation
¶ Corrected capacity of outdoor unit when Indoor / Outdoor unit capacity ratio is in the range of 100
to 130 %
PC units
150 type
Capacity kW
Indoor / Outdoor
unit capacity ratio
Cooling
100 %
45.0
105 %
45.6
110 %
46.1
115 %
46.7
120 %
47.3
125 %
47.8
130 %
48.4
AD units
70 type
Capacity kW
Indoor / Outdoor
unit capacity ratio
Cooling
100 %
22.4
105 %
22.7
110 %
23.0
115 %
23.2
120 %
23.5
125 %
23.8
130 %
24.1
Combinations of outdoor units
Total cooling
67.4 (24)
capacity kW (HP)
Unit
150 type
Cooling
67.4
100 %
Heating
75.0
Cooling
68.2
105 %
Heating
75.4
Cooling
69.1
110 %
Heating
75.8
Cooling
69.9
115 %
Heating
76.2
Cooling
70.8
120%
Heating
76.7
Cooling
71.6
125 %
Heating
77.1
Cooling
72.5
130 %
Heating
77.5
190 type
Capacity kW
Heating
Cooling
Heating
50.0
56.0
63.0
50.3
56.7
63.3
50.6
57.4
63.7
50.8
58.1
64.0
51.1
58.8
64.4
51.4
59.5
64.7
51.7
60.2
65.1
90 type
Capacity kW
Heating
Cooling
Heating
25.0
28.0
31.5
25.1
28.4
31.7
25.3
28.7
31.8
25.4
29.1
32.0
25.6
29.4
32.2
25.7
29.8
32.4
25.8
30.1
32.5
73 (26)
70 type
150 type
90 type
73.0
81.5
73.9
81.9
74.8
82.4
75.7
82.8
76.7
83.3
77.6
83.7
78.5
84.2
II - 7
Design of W-ECO MULTI SYSTEM
78.4 (28)
190 type
70 type
190 type
78.4
88.0
79.4
88.5
80.4
89.0
81.3
89.5
82.3
89.9
83.3
90.4
84.3
90.9
84 (30)
90 type
84.0
94.5
85.1
95.0
86.1
95.5
87.2
96.1
88.2
96.6
89.3
97.1
90.3
97.6