High room temperature standby

MAX
value
This parameter lets you establish the room temperature threshold above which the heat
0
70
pump is disabled; once the threshold has been exceeded, the compressor and pump are
switched off.
High temperature threshold for input water
MAX
value
This parameter indicates the temperature of the input water above which the pump is
switched off and a pre-alarm is generated. After the intervention of the pre-alarm, there
80
is a waiting time of 15 minutes before the pump starts up again. After the third interven-
tion, the machine goes into alarm/lockout. Active also with the pump switched off, and
the chiller in standby. In the latter case, the alarm is generated.
Screensaver configuration
MAX
value
0
2
This parameter indicates the configuration of the screensaver:
• value 0, screensaver disabled;
• value 1, screensaver with visualisation of the dashes (to be used with the control panels
with software prior to version 1.3);
• value 2, screensaver without visualisation of the dashes (to be used with the control
panels with software from version 1.3 onwards).
Modbus supervisor address
MAX
value
0
999
This parameter indicates the Modbus address assigned to the supervisor; this address
will be used in the communication between supervisor and Moducontrol.
Supervisor baud rate
MAX
value
0
2
This parameter indicates the speed of communication between supervisor and
Moducontrol; this speed is set on the basis of the value selected for this parameter:
0 = 9600 bps
1 = 19200 bps
2 = 38400 bps
Parameter function
Parameter function
Parameter function
Parameter function
Parameter function
j j
j
Parameters only visible in the models with DCP installed
Parameters only visible in bicompressor models
Parameters only visible in the models with inverter compressor

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MODUCONTROL and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Table of Contents

Save PDF