Quick Start-Up - Viessmann Vitosol 100-FM SV1F Installation, Operating And Service Instructions

Flat plate solar collectors for sloped roofs, flat roofs, walls and freestanding installation
Table of Contents

Advertisement

Start-up

Quick Start-up

Legend
A Solar collector
B Solar-Divicon (pumping station)
C Overflow container
D Expansion tank
E Solar manual filling pump (optional)
F System fill manifold valve
G Solar storage tank
H Air separator
I Fast air vent c/w shutoff valve
J Solar fluid
K Tank temperature sensor
L Collector temperature sensor(field installed)
M Solar control unit
h
Static head (used to calculate system pressure).
Highest point in system to expansion tank connection.
R Return to collector
S Supply from collector
38
Vitosol 100-FM/200-FM Installation, Operating and Service
Start-up steps
1. Check and adjust nitrogen cushion pressure in the
diaphragm expansion tank D. Calculate cushion
pressure based on formula (see page 37) and charge
cushion pressure as required.
2. Thoroughly flush system through the system fill
manifold F to remove debris and flux residue (see
page 40).
3. Fill system with solar fluid J through the system fill
manifold F using charge pump or hand fill pump E.
CAUTION
Never mix Tyfocor-HTL with alternative heat transfer
media or with water.
4. Fill system to minimum fluid fill pressure (see page 37).
Typical values:
1-storey home: Static head= 10 ft. (3 m)
System fill pressure= 48.5 psig (3.3 bar)
2-storey home: Static head= 20 ft. (6 m)
System fill pressure= 53 psig (3.7 bar)
5. Purge all air from air vents L and H by running
solar loop pump at maximum speed. After system is
completely vented, shut off air vent valve in top of
system.
6. Set system flow rate (see page 42).
7. Provide overflow container C (minimum size should
equal collector fluid volume).
8. Set control settings: Differentials, maximum tank
temperature.
9. Remove protective film from flat plate collectors or
install the tubes.
CAUTION
Remove protective film from flat plate collector ONLY
after all above steps have been completed.
CAUTION
Never flush with water when it is freezing, if no heat
transfer medium is used.
CAUTION
Never drain the system with a vacuum pump.