Hydronic Connections
Supply and Return Piping Configuration
Single array less than or equal to (
collectors
Multiple arrays less than or equal to (
collectors per individual array
Legend
A Collector temperature sensor(field installed)
Collector Supply and Return Piping
For the piping connecting the collectors to the Solar
Divicon pumping station, Viessmann recommends the
use of commercial copper pipe and bronze fittings, or
non-galvanized steel pipe. (PEX or other plastic pipes
are not suitable for solar collector supply and return
piping).
Use only high temperature solder or brazing material
when connecting the copper pipes in the collector
piping. The melting temperature should be above
450°F (232°C).
When laying out the collector array, ensure that air
can be properly vented.
30
) 10x flat plate
) 10x flat plate
Vitosol 100-FM/200-FM Installation, Operating and Service
(continued)
Single array less than or equal to (
collectors
Multiple arrays less than or equal to (
collectors per individual array
Legend
A Collector temperature sensor(field installed)
CAUTION
Do not use galvanized pipes, galvanized fittings or
graphitized gaskets or any type of plastic pipes or
fittings.
Refer to the Vitosol System Design Guidelines for
required flow rates and pipe sizing parameters for
Vitosol-FM collectors.
) 12x flat plate
) 12x flat plate