Mx Actuator Subassembly Components; Product Description; Storage; Table 2.1 - Mx Actuator Subassembly Components - Flowserve Limitorque MX-40 User Instructions

Limitorque mx series electronic actuator
Table of Contents

Advertisement

4
Limitorque MX Maintenance and Spare Parts FCD LMENIM2314-00 – 07/08

2.1 MX Actuator Subassembly Components

Table 2.1 – MX Actuator Subassembly Components
No.
Description
1
Top-mounted handwheel
2
Drive sleeve
3
Worm shaft
Motor
4
Declutch lever
5
Encoder
6
Control panel (CP)
7
8
Control module
9
Optional bases
Thrust base type
• A1 = Standard thrust base
• A1E = Extended-reach thrust base
Baseplate-type B4 with stem nut options type:
10
• B4 = stem nut with variable bore and key
• B4E = extended-reach stem nut with variable bore and key
• BL = splined stem nut (SAE or Involute)
11
Handwheel adapter/handwheel worm gear
12
Side-mounted handwheel (not shown, but available for the MX-10, -20,-85, -140, and -150)
13
Encoder drive cartridge
14
Terminal block

2.1.1 Product Description

Your MX actuator controls the opening and closing travel of valves and other actuated devices. OPEN
and CLOSED limits are protected by an absolute encoder that provides optical sensing of valve position
and measures valve position in both motor and handwheel operation. No battery or backup power
supply is required. Output torque is derived from motor speed, temperature, and voltage. If the preset
torque is exceeded, the motor shuts off. As a result of this reliable and advanced protection technology,
all valve and other actuated devices are protected from potential damage from overload, improper
seating, and foreign obstructions.
A range of control and network options is available and can be easily added to the control capabilities
already available on a standard actuator. Contact your local Limitorque distributor or Limitorque sales
office for further information.

2.1.2 Storage

Storage Recommendations
Your MX actuator is double-sealed and weatherproof as shipped, providing all compartment covers and
cable entry plugs are left intact. Actuators should be stored in a clean, dry, protected warehouse until
ready for installation. If actuators must be stored outdoors, they should be stored off the ground, high
enough to prevent being immersed in water or buried in snow.
Swanson Flo | 800-288-7926 | www.swansonflo.com

Advertisement

Table of Contents
loading

Table of Contents