Refrigerant

16
Before regulation can be commenced, the refrigerant must be defined.
You may select one of the following refrigerants:
1
R12
2
R22
3
R134a
4
R502
5
R717 (ammonia)
6
R13
7
R13b1
8
R23
The refrigerant is selected by keying a figure between 1 and 23. If you push 0, no refrigerant
has been selected.
Warning: Incorrect selction of refrigerant can cause damage to the compressor.
Main function
A subsequent change of refrigerant can only be performed in this way:
- Select new type
- The controller reports an error
- Interrupt supply voltage to the controller
- Wait five seconds
- Reconnect supply voltage
- Regulation can be started again
Other refrigerants?
The function has been prepared for the definition of a refrigerant that differs from the above
mentioned types. This definition can be made by keying the figure "13" plus a number of
subsequent parameters. This setting can only be made with assistance from Danfoss.
Function description RC.1J.Z4.02 © Danfoss 09/1999
9
R500
10
R503
11
R114
12
R142b
13
User-defined
14
R32
15
R227
16
R401A
Rfg. type 1..23
17
R507
18
R402A
19
R404A
20
R407C
21
R407A
22
R407B
23
R410A
___
Rfg. type
___
Rfg. Fac. a1
___
Rfg. Fac. a2
___
Rfg. Fac. a3