Start-up
The circuit to the which the device and the load
will be connected has to be secured by a cable
protection switch in accordance with EN60898-1
(tripping characteristic B or C, max. 16 A rated
current, min. 6 kA interrupting rating, energy
limiting class 3). Installation regulations according
to VDE 0100 and HD382 or 60364 have to be
considered. Users must be able to easily access
the cable protection switch. This must be marked
as disconnecting device for the actuator.
Please observe the hazard information in section
„2 Hazard information" on page 40 during
installation.
Permitted cable cross sections for connecting to the
Multi IO Box:
Rigid cable [mm
0.75 – 2.50
Permitted cable diameter for cable bushings are:
Terminals 1 - 5
8 to 11 mm
48
2
] Flexible cable with/without
ferrule [mm
0.75 – 2.50
Terminal 6
5 to 8 mm