2. Installation

LED Interface Module - 4XLMF (4412LM)

Connect the terminals on TB1 of the LED Interface Module to the corresponding terminals of the RZA-
4XF Remote Annunciator.
Make wiring connections with system power off.
Maximum wire impedance is 50 ohm per wiring connection.
With the MS-4412B the RZA-4XF must be installed in the same room or within 20 feet (6.1 meters) of
the control panel.
The wiring of this module must follow the requirements as specified under "Power-limited Wiring
Requirements" on page 16.
26
J2
SYSTEM TROUBLE
RE-SOUND
TONE
SILENCE
FIRE ALARM ANNUNCIATOR
Front View
Figure 17 Connection of 4XLMF (4412LM) to RZA-4XF
+24V/12V
Out #1
Out #2
Out #3
Out #4
Sysyem Trouble
Sound
Resound
Connect to corresponding
terminals of the RZA-4XF
Remote Annunciator.
Single-gang
Box
Side View
MS-4412B/MS-4424B Instruction Manual PN 15125:G1 10/22/02
Optional Modules