21 Commissioning instructions

Before applying power to the panel, any solenoids or igniting actuators must be physically isolated from
the panel by disconnecting both wires, this will prevent any accidental release of extinguishing gas.
When power is applied and if all connections are correct, only the green Power On and either the
Automatic/Manual or Manual Only indicators should be illuminated.
If any fault indicators are illuminated the wiring to the appropriate input or output should be checked an all
faults cleared before proceeding.
Once the ECU is fault free, it can be configured with the desired options.
Once the ECU has been configured the system should be thoroughly tested to ensure that it responds as
expected and required.
After satisfactory testing, any final connections should be made (such as to the extinguishing release
actuator).
A record of the configuration options that have been set should be recorded in the tables below and
provided as part of the documentation recommended by BS5839:Part 1:2002 section 40.2 b).
CONFIGURATION OPTION
EXTINGUISHING OUTPUT MODE =
ACTIVATION MODE =
FIRST ACTIV. ZONE =
LAST ACTV. ZONE =
RESET INHIBIT TIME =
PRE-REL. DELAY TIME =
EXTING. RELEASE TIME =
PULSED ACTIV. ALARMS ?
STEADY ACTIV. ALARMS ?
RELEASED IND. ON RELEASE INPUT ?
RELEASED IND. ON EXTING RELEASE ?
DELAY ON MANUAL RELEASE ?
NO DELAY ON MANUAL RELEASE ?
PRE-REL DELAY RESET ENABLED ?
PRE-REL DELAY RESET DISABLED ?
RELEASE TIMER ENABLED ?
RELEASE TIMER DISABLED ?
R0V NOT REMOVED ON SYSTEM RESET ?
R0V REMOVED ON SYSTEM RESET ?
EARTH FAULT ENABLED ?
EARTH FAULT DISABLED ?
FAULT OUTPUT ENABLED ?
FAULT OUTPUT DISABLED ?
LOW PRESS. I/P NORMAL ?
LOW PRESS. I/P INVERTED ?
EXTING. O/P 1 LEVEL ?
EXTING. O/P 2 LEVEL ?
TM206
35 of 35
WRITE SETTING