Safety; Mounting - Kidde FireBeta XT+ Operation And Maintenance Manual

Extinguishind coincidence unit
Table of Contents

Advertisement

2

Safety

Suppliers of articles for use at work are required under section 6 of the Health and Safety at
Work act 1974 to ensure as reasonably as is practical that the article will be safe and without
risk to health when properly used.
An article is not regarded as properly used if it is used 'without regard to any relevant
information or advice' relating to its use made available by the supplier.
This product should be installed, commissioned and maintained by trained service personnel
in accordance with the following:
(i)
IEE regulations for electrical equipment in buildings
(ii)
Codes of practice
(iii)
Statutory requirements
(iv)
Any instructions specifically advised by the manufacturer
According to the provisions of the Act you are therefore requested to take such steps as are
necessary to ensure that you make any appropriate information about this product available
to anyone concerned with its use.
This equipment is designed to operate from 230V 50Hz mains supplies and is of class 1
construction. As such it must be connected to a protective earth conductor in the fixed wiring
of the installation and a readily accessible double pole disconnect device meeting the
requirements of EN60950/IEC950 which disconnects live and neutral simultaneously shall be
incorporated in the fixed wiring. Switch disconnect devices such as MK Sentry 63A or similar
are suitable for this.
WARNING: Failure to ensure that all conductive accessible parts of this equipment are
adequately bonded to the protective earth will render the equipment unsafe.
This control panel is environmental class A and is designed for indoor use only at
temperatures between -5
95%.
The IP rating for the enclosure is IP30.
Operation outside of these limits may render the equipment unsafe.
3

Mounting

The ECU should be mounted on a dry, flat surface, at eye height to the displays and in a level
position such that the enclosure is not distorted.
Screws or bolts of a minimum of 5mm diameter must be used to mount the enclosure in all
four mounting positions.
It should be positioned in an accessible place as agreed with the end user.
Suitable fixings should be used at all fixing points such that the unit is securely mounted and
is not liable to move once fixed.
The ECU should not be mounted in another enclosure or near sources of excessive heat.
Cables should be connected using suitable cable glands fitted to the knockouts provided. If
additional cable entry points are required, all swarf and debris caused by drilling of additional
cable entries must be cleared before power is applied to the panel.
TM206
0
0
C (+/- 3) and +40
C (+/- 2) and with a maximum relative humidity of
5 of 35