Disable Extract Output; Turn On Extract Output; Single Input Activation; Double Input Activation - Kidde FireBeta XT+ Operation And Maintenance Manual

Extinguishind coincidence unit
Table of Contents

Advertisement

Turn the ENABLE CONTROL keyswitch off to leave the disablement active. To re-enable the Released
relay output repeat the procedure above.

15.2.6 Disable Extract output

To disable the Extract relay output, press the UP button on the module while at access level 2 until the
display shows:
Press the ENTER button to select this function. The display will show:
The yellow disabled LED will be lit.
Turn the ENABLE CONTROL keyswitch off to leave the disablement active. To re-enable the Extract
relay output repeat the procedure above.

15.2.7 Turn on Extract output

To turn on the extract relay output, press the DOWN button on the module while at access level 2 until
the display shows:
Press the ENTER button to select this function. The display will show:
The yellow disabled LED on the module that has been disabled will be lit.
Turn the ENABLE CONTROL keyswitch off to leave the Extract output active. To turn off the Extract
output, repeat the procedure above.
Note:
The extract output does not turn off when the module is reset.

15.3 Single input activation

st
Upon activation of a single monitored activation input, the activated LED will flash, the 1
stage relay
st
contact will operate, the 1
stage sounder will operate and the LCD will show:
st
Pressing the Silence alarm button on the detection module will turn off the 1
stage sounder output.

15.4 Double input activation

Upon activation of a second monitored activation input with the ECU in Automatic/Manual mode with the
Hold inputs inactive and where the Disable Extinguishing function has not been invoked, the ECU will
respond as follows:
TM206
29 of 35
Issue 1.0