4

Technical specification

Table 1 - Electrical specifications
ITEM
Mains supply
Mains supply fuse
Power supply rating
Maximum ripple current
Battery type (Yuasa NP)
Battery charge voltage
Battery charge current
Current draw in mains fail condition
Maximum current draw from
batteries
Aux 24V output
1
st
and 2
nd
stage Sounder outputs
Fault relay contact rating
Fire relay contact rating
First stage contact rating
Second stage contact rating
Extract contact rating
Terminal capacity
Number of sounders per circuit
Monitored input end of line
Sounder circuit end of line
Extinguishing output end of line
No. of sounder circuits (2)
Extinguishing release outputs (2)
Extinguishing release delay
Extinguishing release duration
Cabling
Monitored inputs normal threshold
(Allowable EOL)
Monitored inputs alarm threshold
Monitored inputs s/c threshold
Status unit/Ancillary board
connection
Status unit power output
ELECTRICAL RATING
230V AC, 50Hz +10% - 15% (100 Watts maximum)
T2A L250V
4 Amps including battery charge 28V +/- 2V
200 millivolts
2 x 12 Volt sealed lead acid in series
27.6VDC nominal (temperature compensated)
1,5A maximum
60 milliamps quiescent – 107 milliamps full alarm
4 Amps
Fused at 500mA with electronic fuse
21 to 28V DC Fused at 1A with electronic fuse
5 to 30VDC 1A Amp maximum for each
5 to 30VDC 1A Amp maximum for each
5 to 30VDC 1A Amp maximum for each
5 to 30VDC 1A Amp maximum for each
5 to 30VDC 1A Amp maximum for each
2
2
0.5mm
to 2.5mm
solid or stranded wire
Dependent on type and current consumption
6K8 +/- 5% ½ Watt resistor
10K +/- 5% ¼ Watt resistor
1N4004 Diode
21 to 28V DC
21 to 28V DC. Fused at 1 Amp
Adjustable 0 to 60 seconds (+/- 10%)
Adjustable 60 to 300 seconds
FP200 or equivalent (Maximum capacitance 1µF, max
inductance 1Mh)
10K ohm to 2K ohm
2K ohms to 150 ohms +/-5%
140 ohms to 0 ohms +/-5%
Two wire RS485 connection (EIA-485 specification)
21 to 28V DC, Fused at 500mA with electronic fuse
TM206
COMMENT
Replace only with similar type
With main power source disconnected
200 milliamp maximum continuous load
1.0 Amp total load over all circuits
Maximum ratings not to be exceeded
Maximum ratings not to be exceeded
Maximum ratings not to be exceeded
Maximum ratings not to be exceeded
Maximum ratings not to be exceeded
See table 2 for sounder types
Supplied in terminals
Supplied in terminals
Supplied in terminals
st
1 x 1
stage and 1 x 2
1 Amp maximum load –for 5 minutes
3 Amps for 20 milliseconds
5 second steps
5 second steps
Metal cable glands must be used
Maximum of 7 units per area- RS485
data cable.
300 milliamp maximum load
7 of 35
COMMUNICATION
PARAMETERS
Standard European mains
connection
Modulated DC
Modulated DC
Voltage reversing DC
Volt free changeover contact
Volt free changeover contact
Volt free changeover contact
Volt free changeover contact
Volt free changeover contact
nd
stage
Voltage reversing DC with
calibration facility
(EIA-485 specification)
Issue 1.0