Release Timer; R0V Not Removed On Reset - Kidde FireBeta XT+ Operation And Maintenance Manual

Extinguishind coincidence unit
Table of Contents

Advertisement

To change to this, press the ENTER button.
To save the settings, slide the WRITE ENABLE switch gently to the right.
It will now be possible to reset the module during the pre-release delay but not while the extinguishing
outputs have operated or until after expiry of the reset inhibit time.
Note:
Disabling the Pre-release delay reset does not comply with the requir3ements of EN12094-1.

14.10 Release timer

The release timer can be disabled such that once the Extinguishing output has operated; it remains
operated until the system is reset.
To disable the release timer, switch on the ENABLE CONTROLS keyswitch and slide the WRITE
ENABLE switch on the module to be configured gently to the left. Press the ENTER button on the ECU
then press the DOWN button until the display shows:
Press the ENTER button and the display will show:
o disable the release timer, press the ENTER button.
T
To save the settings, slide the WRITE ENABLE switch gently to the right.
With the release timer disabled, the Extinguishing outputs will remain operated until the system is reset.

14.11 R0V not removed on reset

It is possible to configure the AUX24V output on the ECU to be removed for a few seconds when the
system is reset.
The factory default setting is for the Aux24V output not to be removed when the system is reset.
To configure the module such that Aux24V output is removed for a few seconds when the system is
reset, switch on the ENABLE CONTROLS keyswitch and slide the WRITE ENABLE switch on the
module to be configured gently to the left. Press the ENTER button on the ECU then press the DOWN
button until the display shows:
Press the ENTER button and the display will show:
To select this option, press the ENTER button.
To save the settings, slide the WRITE ENABLE switch gently to the right.
With the release module configured to remove the R0V output on system reset, the Aux 24V output will
be removed for a few seconds when the reset button is pressed.