9.3 resetting a Detector's Wireless Interconnect
Settings
If you experience a delay or problem during wireless interconnection setup, you might need to start over as
if the detector is first removed from its packaging. Also, this "out-of-box" mode can be used to attempt to
reset/clear a network error condition.
NOTE: The magnetic switch is disabled when network is open and GREEN LED is glowing on/off. Press
and hold Test/Hush button for 4 seconds to close network before attempting to reset device to the "out-of-
box" mode.
1. Place and hold a magnet for 4 seconds on the cover at the designated location per Figure 5. The de-
tector will chirp once when the magnet is detected, then the detector will chirp twice and the button will
start flashing the RED LED rapidly to indicate System Test Mode has been entered.
2. Press and hold the Test/Hush button for approximately eight seconds while the RED LED is rapidly
flashing. After four seconds, two beeps will occur (do not release the button). After eight seconds, three
beeps will occur. The button can now be released.
3. Observe two cycles of RED LED on/off, one cycle of GREEN LED on/off
4. The RED LED will begin fading on/off every three seconds.
5. If no further steps are taken within 15 minutes of resetting the detector to "Out-of-Box" mode, the RED
LED will fade on/off for approximately 30-40 seconds, and the interconnect function will turn off. The
detector will then perform as a single station detector.
22
P/N 466-5308 • REV A • ISS 09MAY17
MAGNET
PLACEMENT
LOCATION
Figure 5
©2017 United Technologies Corporation