9.2 Adding Detectors to an Existing Wireless
Interconnected Network
For various reasons, you might want to add additional detectors to your existing wireless interconnection
network.
1. Remove the new detector from its packaging.
2. Place and hold a magnet for four seconds on the cover of an existing detector in the network at the
designated location per Figure 5. The detector will beep once when the magnet is detected, then the
detector will beep twice and will start flashing the RED LED rapidly to indicate the detector is in System
Test Mode.
3. Push and hold the test button on the same detector (in System Test Mode) until two beeps are heard
(approximately four seconds), and then release the button.
The button-pushed detector will cause the GREEN LED to fade on/off on each detector in the exist-
ing network to signal that the wireless interconnection network has been opened.
NOTE: From this point, you have fifteen (15) minutes to power up the new detector.
4. Power up the new wireless detector by twisting the detector onto the mounting bracket (trim plate) to
activate the battery, or by carefully turning the red activation wheel with a screwdriver. See Figure 4.
After initial GREEN LED on/off sequence, the new detector's RED LED will fade on/off every three
seconds as it searches for the network.
A fast GREEN LED flickering, followed by a slow GREEN LED fading on/off confirms the new detec-
tor has found and joined the existing wireless interconnection network.
5. Wait fifteen (15) minutes for the network setup to timeout, OR to immediately close the network, push
and hold the test button on any device enrolled in the network until two beeps are heard (approximately
four seconds), and then release the button.
GREEN LED flashes once every 60 seconds on the new detector to indicate normal operation.
6. After selecting the proper location for your detector, attach the mounting bracket to the wall or ceiling.
To ensure aesthetic alignment of the detector with the hallway, or wall, the "A" line on the mounting
bracket must be parallel with the hallway when ceiling mounted or horizontal when wall mounted.
Install the detector fully on the mounting bracket (trim plate) by rotating the detector in a clockwise
direction. NOTE: The detector will mount to the bracket in four positions (every 90 degrees).
7. The detector is now activated. After installation / activation, test your detector as described in Opera-
tion and Testing section.