Set Up A Wireless Detector Network (Wireless Interconnect) - Interlogix SDX-135Z User Manual

Wireless smoke detector with heat and freeze sensor
Hide thumbs Also See for SDX-135Z:
Table of Contents

Advertisement

WIrELESS
These models have wireless detector interconnect capability. When one interconnected detector sounds an
alarm, all other compatible wireless detectors in the wireless detector network will alarm.
A maximum of 24 compatible devices may be interconnected in a multiple station arrangement in conjunc-
tion with a compatible panel.
This detector is not designed to be interconnected with other manufacturer's products, unless otherwise
specified.
WIrELESS INTErCONNECT MODEL COMpATIbILITy
The following Interlogix models can be interconnected using wireless interconnect:
SDX-135Z, CDX-135Z
Maximum distance between wireless interconnect models is 300 feet in open air.
9.1 Set up a Wireless Detector Network (Wireless
Interconnect)
1. Remove all wireless detectors from their packaging (suggest using a table and activating all detectors in a group).
2. Power on all detectors by attaching the detectors onto the mounting bracket (trim plate) to activate the
battery, or by carefully turning the red activation wheel with a screwdriver. See Figure 4.
• The GREEN LED will fade on and off once, then the RED LED will begin fading on/off every 3 seconds.
NOTE: If no further steps are taken within 15 minutes of initial power up, the wireless function will turn
off. The detector will then perform as a single station detector.
P/N 466-5308 • REV A • ISS 09MAY17
Figure 4
©2017 United Technologies Corporation
19