Function
Selections or
Prompt
Range of Setting
Lower Display
Upper Display
DISABLE
ALARM 1
ALARM 2
ALARM12
DIAGNOST
DISABLE
ALARM 1
ALARM 2
62
DISABLE—Disables blocking
ALARM 1—Blocks alarm 1 only
ALARM 2—Blocks alarm 2 only
ALARM12—Blocks both alarms
ATTENTION When enabled on power up or initial enabling via
configuration, the alarm will not activate unless the parameter
being monitored has not been in an alarm condition for a
minimum of one control cycle (167 ms).
DIAGNOSTIC—Monitors the Current Output and/or Auxiliary
Output for an open circuit condition. If either of these two outputs
falls below about 3.5 mA, then an Alarm is activated. This
configuration is in addition to whatever was selected for
AxSxTYPE.
DISABLE—Disables Diagnostic Alarm
ALARM 1—Alarm 1 is diagnostic alarm
ALARM 2—Alarm 2 is diagnostic alarm
UDC3200 Universal Digital Controller Operator Manual
Parameter Definition
04/08