Honeywell UDC3200 series Operator's Manual page 60

Universal digital controller
Hide thumbs Also See for UDC3200 series:

Advertisement

Function
Selections or
Prompt
Range of Setting
Lower Display
Upper Display
Low Scale Value
LOW VAL
within the range of
the selected
variable to
represent the
minimun output (0
or 4 mA)
HIGH VAL
High Scale Value
within the range of
the selected
variable to
represent the
maximum output
(20 mA)
DIG INP1
NONE
TO MAN
TO LSP
TO 2SP
TO 3SP
TO DIR
TO HOLD
TO PID2
PV 2IN
RERUN
54
AUXILIARY OUTPUT LOW SCALING FACTOR— This is a value
in engineering units used to represent all AUX OUT parameters
except Output.
For Output, this is a value in percent and can be any value
between –5 % and +105 %. However, keep in mind that relay
output types can only be scaled 0 % to 100 %.
AUXILIARY OUTPUT HIGH SCALING FACTOR— This is a value
in engineering units used to represent all AUX OUT parameters
except Output.
For Output, this is a value in percent and can be any value
between –5 % and +105 %. However, keep in mind that relay
output types can only be scaled 0 % to 100 %.
DIGITAL INPUT 1 SELECTIONS—All selections are available for
Input 1. The controller returns to its original state when contact
opens, except when overruled by the keyboard.
NO DIGITAL INPUT SELECTIONS
TO MANUAL—Contact closure puts the affected loop into manual
mode. Contact open returns controller to former mode.
TO LOCAL SETPOINT—When a remote setpoint is configured,
contact closure puts the controller into local setpoint 1. When
contact opens, the controller returns to former operation—local or
remote setpoint—unless SP Select key is pressed while digital
input is active. If this happens, the controller will stay in the local
setpoint mode when contact opens.
TO LOCAL SETPOINT TWO—Contact closure puts the controller
into local setpoint 2.
TO LOCAL SETPOINT THREE—Contact closure puts the
controller into local setpoint 3.
TO DIRECT ACTION—Contact closure selects direct controller
action.
TO HOLD—Contact closure suspends Setpoint Program or
Setpoint Ramp. When contact reopens, the controller starts from
the Hold point of the Ramp/Program unless the Ramp/Program
was not previously started via the
This selection applies to either loop.
TO PID2—Contact closure selects PID Set 2.
PV=INPUT 2—Contact closure selects PV = Input 2.
RERUN--Allows the Setpoint Programmer to be reset to the initial
segment of its current cycle, unit stays in previous mode.
UDC3200 Universal Digital Controller Operator Manual
Parameter
Definition
Run
Run
Run
Hold
Hold
Hold
key.
04/08