Honeywell UDC3200 series Operator's Manual page 56

Universal digital controller
Hide thumbs Also See for UDC3200 series:

Advertisement

Function
Selections or
Prompt
Range of Setting
Lower Display
Upper Display
LAST
(Note 3)
F'SAFE
SP HiLIM
0 to 100 % of PV
span in
(Note 4)
engineering units
SP LoLIM
0 to 100 % of PV
span in
(Note 4)
engineering units
ACTION
DIRECT
REVERSE
OUT RATE
ENABLE
DISABLE
PCT/M UP
0 to 9999 % per
minute
PCT/M DN
0 to 9999 % per
minute
OUTHiLIM
0 % to 100 %
–5 % to 105 %
OUTLoLIM
0 % to 100 %
–5 % to 105 %
Within the range of
I Hi LIM
the output limits
(Note 5)
I Lo LIM
Within the range of
the output limits
(Note 5)
–5 to 105 % of
DROPOFF
output
(Note 5)
50
LAST OUTPUT—At power-up in automatic mode, the motor
position will be the last one prior to power down. When the unit
goes into FAILSAFE, it will stay in automatic mode; motor will not
be driven to the configured failsafe position.
FAILSAFE OUTPUT—At power-up in manual mode, the motor will
be driven to either the 0 % or 100 % output position, whichever is
selected at prompt FAILSAFE. For Burnout/None, when the unit
goes into FAILSAFE, it will go to manual mode; motor will be driven
to the configured failsafe position.
SETPOINT HIGH LIMIT—This selection prevents the local and
remote setpoints from going above the value selected here. The
setting must be equal or less than the upper range of the PV.
SET POINT LOW LIMIT—This selection prevents the local and
remote setpoints from going below the value selected here. The
setting must be equal or greater than the lower range of the PV.
CONTROL OUTPUT DIRECTION—Select direct or reverse output
action.
DIRECT ACTING CONTROL—The controller's output increases
as the process variable increases.
REVERSE ACTING CONTROL—The controller's output
decreases as the process variable increases.
OUTPUT CHANGE RATE—Enables or disables the Output
Change Rate. The maximum rate is set at prompt PCT/M UP or
PCT/M DN. Only available for PID-A, PID-B, PD+MR control
algorithms.
ENABLE—Allows output rate.
DISABLE—Disables output rate.
OUTPUT RATE UP VALUE—This selection limits the rate at which
the output can change upward. Enter a value in percent per
minute. Appears only if OUT RATE is enabled. "0" means no output
rate applied.
OUTPUT RATE DOWN VALUE—This selection limits the rate at
which the output can change downward. Enter a value in percent
per minute. Appears only if OUT RATE is enabled. "0" means no
output rate.
HIGH OUTPUT LIMIT—This is the highest value of output beyond
which you do not want the controller automatic output to exceed.
For relay output types.
For current output types.
LOW OUTPUT LIMIT—This is the lowest value of output below
which you do not want the controller automatic output to exceed.
For relay output types.
For current output types.
HIGH RESET LIMIT—This is the highest value of output beyond
which you do not want reset action to occur
LOW RESET LIMIT—This is the lowest value of output beyond
which you do not want reset action to occur.
CONTROLLER DROPOFF VALUE—Output value below which
the controller output will drop off to the low output limit value set in
prompt OUTLoLIM.
UDC3200 Universal Digital Controller Operator Manual
Parameter Definition
04/08