TABLE IV - Options
Approvals
Future Options
TABLE V - Product Manuals
Manuals
Certificate
TABLE VI
No Selection
2.3 Control and Alarm Relay Contact Information
Control Relays
ATTENTION
Control relays operate in the standard control mode (that is, energized when output state is on).
Unit Power
Off
On
Alarm Relays
ATTENTION
Alarm relays are designed to operate in a failsafe mode (that is, de-energized during alarm
sate). This results in alarm actuation when power is OFF or when initially applied, until the unit
completes self-diagnostics. If power is lost to the unit, the alarms will de-energize and thus the
alarm contacts will close.
Unit
Power
Off
On
6
CE (Standard)
CE, UL and CSA
None
Tags
Linen Customer ID Tag - 3 lines w/22 characters/line
Stainless Steel Customer ID Tag - 3 lines w/22 characters/line
None
None
None
Product Information on CD - All Languages
English Manual
French Manual
German Manual
Italian Manual
Spanish Manual
None
Certificate of Conformance (F3391)
None
Figure 2-1 Model Number Interpretation
Table 2-1 Control Relay Contact Information
Control Relay
Wiring
N.O.
N.C.
N.O.
N.C.
Table 2-2 Alarm Relay Contact Information
Alarm Relay
Variable NOT in Alarm State
Wiring
Contact
N.O.
N.C.
N.O.
N.C.
UDC3200 Universal Digital Controller Operator Manual
Control Relay
Contact
Open
Closed
Open
Closed
Closed
Open
Relay
Indicators
Open
Off
Closed
Closed
Off
Open
0 _ _ _ _
1 _ _ _ _
_ 0 _ _ _
_ T _ _ _
_ S _ _ _
_ _ 0 _ _
_ _ _ 0 _
_ _ _ _ 0
0 _
E _
F _
G _
I _
S _
_ 0
_ C
0 _
Output #1 or #2
Indicator Status
Off
Off
On
Off
On
Variable in Alarm State
Relay
Indicators
Contact
Open
Off
Closed
Open
On
Closed
04/08