2 SIVACON S8 – System overview
The interaction of the components described below results
in an optimal low-voltage switchboard with advantages as
regards:
Tab. 2/1:
Technical data, standards and approvals for the SIVACON S8 switchboard
Standards and approvals
Standards and regulations
Approvals
Technical data
Installation conditions
Rated operating voltage (U
Dimensioning of creepage
distances and clearances
Main busbars, horizontal
Rated device currents
Internal separation
IP degree of protection
Mechanical strength
Dimensions
8
SIVACON S8 Planning Principles – SIVACON S8 – System overview
Power switchgear and controlgear assembly
(design verification)
Test of internal fault behaviour (internal arc)
Induced vibrations
Protection against electric shock
Europe
Russia, Belarus, Kasakhstan
China
Det Norske Veritas
Lloyds Register of Shipping
Shell conformity
Indoor installation, ambient temperature in the
24-h mean
Main circuit
e)
Rated impulse withstand voltage U
Rated
insulation voltage (U
)
i
Degree of pollution
Rated current
Rated peak withstand current (I
Rated short-time withstand current (I
Circuit-breakers
Cable feeders
Motor feeders
IEC 61439-2
BS EN 61439-2
in accordance with IEC 60529
IEC 62262
Height (without base)
Height of base (optional)
Cubicle width
Depth (single-front)
• Safety - integrated
• Economic efficiency - right from the start
• Flexibility – through modularity
IEC 61439-2
DIN EN 61439-2-2
VDE 0660-600-2
IEC/TR 61641
DIN EN 60439-1 Supplement 2
VDE 0660-500 Supplement 2
IEC 60068-3-3
IEC 60068-2-6
IEC 60068-2-57
IEC 60980
KTA 2201.4
Uniform Building Code (UBC), Edition 1997 Vol. 2,
Ch. 19, Div. IV
EN 50274 (VDE 0660-514)
CE marking and EC Declaration of Conformity
EAC
CCC
DNV GL Type Approval Certificate
LR Type Approval Certificate
"DEP Shell"
+ 35 °C
(-5 °C to + 40 °C)
Up to 690 V (rated frequency f
8 kV
imp
1,000 V
3
Up to 7,010 A
)
Up to 330 kA
pk
)
Up to 150 kA, 1s
cw
Up to 6,300 A
Up to 630 A
Up to 630 A
Form 1 to form 4
Up to form 4 type 7
Ventilated up to IP43
Non-ventilated IP54
Up to IK10
2,000, 2,200 mm
100, 200 mm
200, 350, 400, 600, 800, 850, 1,000, 1,200, 1,400 mm
500, 600, 800, 1,000, 1,200 mm
50 Hz)
n
Need help?