6.2

Fixed-mounted design with

front cover
The front covers, which are easy to install, allow for the
implementation of cubicles with uniform front surfaces
(Fig. 6/2). Optionally a glass door can be used. The profile
bar design or flat copper design of the distribution busbar
allows tapping in the smallest grids. Furthermore, connec-
tions to the distribution busbars by means of cables, wires
or busbars are possible without any need of drilling or
punching. This ensures maximum flexibility also for later
expansions.
General cubicle characteristics
Tab. 6/7 summarizes the general cubicle characteristics.
The switching devices are installed on modular device
holders of graduated depth. These can be equipped with
circuit-breakers, switch-disconnectors with fuses or modu-
lar installation devices. Different switching device group-
ings into one module are also possible. Modules are at-
tached to the device holder and directly connected to the
cubicle busbar.
To the front, the devices are equipped with front covers.
Operation is effected through the cover. The cable connec-
tion is effected at the device or, in cases of higher require-
ments, at special connection terminals. For individual
expansion, the system offers freely assignable device
holders.
Tab. 6/7:
General cubicle characteristics for fixed-mounted cubicles with front cover
Application range
Degrees of protection
Cubicle dimensions
Device compartment
Form of internal separation
Design options
1)
Cubicle with degree of protection less than or equal to IP31 is also possible without an additional cubicle high door
Fig. 6/2:
Cubicles for fixed mounting with front cover
- Incoming feeders up to 630 A
- Outgoing cable feeders up to 630 A
- Modular installation devices
- Up to IP43
- IP54
- Cubicle height
- Cubicle width (front connection in the cubicle)
- Height
- Width
- Form 1, 2b, 3b, 4a, 4b
- Fixed-mounted module with front cover
- Mounting kit for modular installation devices
- Empty slot, device compartment
SIVACON S8 Planning Principles – Cubicles in fixed-mounted design
Ventilated
Non-ventilated
2,000, 2,200 mm
1,000, 1,200 mm
1,600, 1,800 mm
600 mm
Door,
1)
viewing door cubicle high
1
2
3
4
5
6
7
8
9
10
11
59

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents