4.3.2 Withdrawable unit compartment in
SFD
The vertical distribution busbar is covered test finger
proofed (IP2X). Phase separation is possible. No connection
work is required in the compartment (Fig. 4/8). The internal
separation options up to form 4b lead to a high degree of
personal safety. Connection is effected in a separate cable
connection compartment. The connection data for main
circuits are stated in Tab. 4/9, those for auxiliary circuits in
Tab. 4/10 and the number of available auxiliary contacts in
Tab. 4/11.
Tab. 4/9:
Connection data for the main circuit
Front connection in cubicle
Rear connection in cubicle
Tab. 4/10:
Connection data for the auxiliary circuit
Type
Push-in terminal connection
Screw connection
Tab. 4/11:
Number of available auxiliary contacts for withdrawable
units in SFD
Withdrawable unit
height
≥ 100 mm
≥ 150 mm
40
SIVACON S8 Planning Principles – Universal mounting design
Withdrawable unit
height
≥ 100 mm
100 mm
≥ 150 mm
Terminal size
2
4 mm
2
6 mm
Number of available auxiliary contacts (rated current 10 A / 250 V)
Control plug type
Without communication
12-pole
12
24-pole
24
32-pole
32
40-pole
40
Fig. 4/8:
Open withdrawable unit compartments in SFD
Nominal feeder current
Terminal size
≤ 35 A
16 mm
≤ 63 A
35 mm
≤ 120 A
70 mm
≤ 160 A
95 mm
≤ 250 A
150 mm
≤ 35 A
16 mm
≤ 250 A
-
With PROFIBUS
9
21
29
37
Maximum
connection cross
section
2
-
2
-
2
-
2
-
2
-
2
-
1 x 185 mm
2 x 120 mm
With PROFINET
12
24
-
-
2
2