Tab. 4/21:
Minimum withdrawable unit sizes for:
fuseless motor feeders, 400 V, CLASS 10,
with overload relay, type 2 at 50 kA
Small withdrawable unit
Minimum withdrawable unit size at 35 °C ambient
Motor
Height 150 mm
power P
Direct
(AC-2/AC3)
contactor
0.25 kW
¼, ½
0.37 kW
¼, ½
0.55 kW
¼, ½
0.75 kW
¼, ½
1.1 kW
¼, ½
1.5 kW
¼, ½
2.2 kW
¼, ½
3 kW
¼, ½
4 kW
¼, ½
5.5 kW
¼, ½
7.5 kW
¼, ½
11 kW
½
15 kW
½
18.5 kW
½
22 kW
½
30 kW
-
Normal withdrawable unit
Minimum withdrawable unit height at 35 °C
Motor
power P
Direct contactor
(AC-2/AC3)
0.25 kW
100 mm
0.37 kW
100 mm
0.55 kW
100 mm
0.75 kW
100 mm
1.1 kW
100 mm
1.5 kW
100 mm
2.2 kW
100 mm
3 kW
100 mm
4 kW
100 mm
5.5 kW
100 mm
7.5 kW
100 mm
11 kW
100 mm
15 kW
100 mm
18.5 kW
150 mm
22 kW
150 mm
30 kW
150 mm
37 kW
150 mm
45 kW
150 mm
55 kW
300 mm
75 kW
300 mm
90 kW
300 mm
110 kW
400 mm
132 kW
500 mm
160 kW
500 mm
200 kW
700 mm
250 kW
700 mm
1)
Type: ¼ = small withdrawable unit size ¼
½ = small withdrawable unit size ½
48
SIVACON S8 Planning Principles – Universal mounting design
1)
temperature
Height 200 mm
Reversing
Direct
Reversing
circuit
contactor
circuit
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
½
½
½
½
½
½
-
½
½
-
½
½
-
½
-
ambient temperature
Reversing
Star-delta
circuit
100 mm
150 mm
100 mm
150 mm
100 mm
150 mm
100 mm
150 mm
100 mm
150 mm
100 mm
150 mm
100 mm
150 mm
100 mm
150 mm
100 mm
150 mm
100 mm
150 mm
100 mm
150 mm
100 mm
150 mm
100 mm
150 mm
150 mm
200 mm
150 mm
200 mm
250 mm
250 mm
250 mm
250 mm
250 mm
250 mm
400 mm
400 mm
400 mm
400 mm
400 mm
400 mm
500 mm
500 mm
500 mm
700 mm
500 mm
700 mm
700 mm
700 mm
700 mm
700 mm
Tab. 4/22:
Minimum withdrawable unit sizes for:
fuseless motor feeders, 400 V, CLASS 10,
with SIMOCODE, type 2 at 50 kA
1)
Small withdrawable unit
Minimum withdrawable unit size at 35 °C ambient
Motor
Height 150 mm
power P
Direct
Reversing
(AC-2/AC3)
contactor
circuit
0.25 kW
½
½
0.37 kW
½
½
0.55 kW
½
½
0.75 kW
½
½
1.1 kW
½
½
1.5 kW
½
½
2.2 kW
½
½
3 kW
½
½
4 kW
½
½
5.5 kW
½
½
7.5 kW
½
½
11 kW
½
½
15 kW
-
-
18.5 kW
-
-
22 kW
-
-
30 kW
-
-
Normal withdrawable unit
Minimum withdrawable unit height at 35 °C
Motor
power P
Direct
(AC-2/AC3)
contactor
0.25 kW
100 mm
0.37 kW
100 mm
0.55 kW
100 mm
0.75 kW
100 mm
1.1 kW
100 mm
1.5 kW
100 mm
2.2 kW
100 mm
3 kW
100 mm
4 kW
100 mm
5.5 kW
100 mm
7.5 kW
100 mm
11 kW
150 mm
15 kW
150 mm
18.5 kW
200 mm
22 kW
200 mm
30 kW
200 mm
37 kW
200 mm
45 kW
200 mm
55 kW
300 mm
75 kW
300 mm
90 kW
300 mm
110 kW
400 mm
132 kW
500 mm
160 kW
500 mm
200 kW
600 mm
250 kW
600 mm
1)
Type: ¼ = small withdrawable unit size ¼
½ = small withdrawable unit size ½
temperature
Height 200 mm
Direct
Reversing
contactor
circuit
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
¼, ½
½
½
½
½
½
-
½
-
½
-
ambient temperature
Reversing
Star-delta
circuit
100 mm
150 mm
100 mm
150 mm
100 mm
150 mm
100 mm
150 mm
100 mm
150 mm
100 mm
150 mm
100 mm
150 mm
100 mm
150 mm
100 mm
150 mm
100 mm
150 mm
100 mm
150 mm
150 mm
150 mm
150 mm
200 mm
250 mm
250 mm
250 mm
250 mm
250 mm
250 mm
250 mm
250 mm
250 mm
250 mm
400 mm
400 mm
400 mm
400 mm
400 mm
400 mm
500 mm
500 mm
500 mm
700 mm
500 mm
700 mm
700 mm
700 mm
700 mm
700 mm

Hide quick links: