In-Line Switch-Disconnectors Sasil Plus With Fuses - Siemens Sivacon S8 Planning Information

Hide thumbs Also See for Sivacon S8:
Table of Contents

Advertisement

5.2
In-line switch-disconnectors
SASIL plus with fuses
Cubicles with pluggable in-line switch-disconnectors can
also be equipped with SASIL plus in-line units (Fig. 5/3)
produced by Jean Müller.
Rating data of the vertical distribution busbar SASIL
plus
The vertical distribution busbars with the phase conductors
L1, L2, L3 are arranged at the back of the cubicle. The PE, N
or PEN busbars are arranged in the cable connection com-
partment. In the case of 4-pole feeders, the N conductor is
allocated to the phase conductors L1, L2, L3 at the back of
the cubicle. The vertical distribution busbar is covered test
finger proofed (IP2X). The rated data are stated in Tab. 5/8.
Rating data of the SASIL plus cable feeders
Apart from the space requirements for additional built-in
elements (Tab. 5/9), the derating factor stated in Tab. 5/10
is to be set for determining the permissible operating
current of a fuse link. The space requirements for the cable
feeders of the different in-line units depend on the nominal
device current (Tab. 5/11).
Tab. 5/11:
Rating data of the SASIL plus cable feeders
Nominal device
Size
current
00
160 A
1
250 A
2
400 A
3
630 A
1)
Rated current with fuse link = nominal device current
The configuration rules stated in the following are to be observed
Space requirements of the in-line unit (height)
3-pole
50 mm
75 mm
150 mm
150 mm
Fig. 5/3:
Pluggable in-line switch-disconnectors SASIL plus
Tab. 5/8:
Rating data of the vertical distribution busbar SASIL plus
Distribution busbar cross section
Rated current at 35 °C ambient
temperature
Rated short-time withstand
1)
current I
(1 sec)
cw
1)
Rated conditional short-circuit current I
Tab. 5/9:
Additional built-in elements for SASIL plus
Built-in elements
Height in mm
Blanking cover for
50, 75, 150,
empty slots
300
150, 200, 300,
Device compartment
450, 600
(mounting
plate with
200, 300, 450,
compartment door)
600
Tab. 5/10:
Derating factors for SASIL plus fuse links
Nominal current of fuse link
I
≤ 32 A
n
32 A < I
≤ 160 A
n
160 A < I
≤ 630 A
n
1)
4-pole
100 mm
150 mm
300 mm
300 mm
SIVACON S8 Planning Principles – In-line design, plug-in
2
2
60 x 10 mm
80 x 10 mm
1,560 A
2,100 A
50 kA
50 kA
= 100 kA
cc
Version
Metal
Without power tapping,
usable overall device
depth 180 mm
With power tapping,
usable overall device
depth 180 mm
Derating factor F
1
0.76
0.81
1)
Rated current
at 35 °C ambient temperature
122 A
203 A
324 A
510 A
1
2
3
4
5
6
7
8
9
10
11
53