Technical Specifications; U Models - CyberPower PDU81001 User Manual

Switched metered by outlet/metered by outlet series/switched/monitored 1u/2u/0u series
Hide thumbs Also See for PDU81001:
Table of Contents

Advertisement

Product Features (2U Models)
Front Panel Description
NEMA Type
IEC Type
A. AC Inlet/ AC Power Cord - Used to connect PDU to utility
power or UPS.
B. AC Output Receptacles - Provides power for connected
equipment.
C. Status Indicator - Indicates the condition of the PDU (eg.
load or environment status).
D. Circuit Breaker – Provides overload protection.
E. ENVIROSENSOR/ Daisy Chain (In) Port (RJ45 modular port)
– Used for ENVIROSENSOR or chaining to previous PDU.
F. USB Port - Used to upgrade the firmware via a flash drive.
G. Serial Port (RJ45 modular port) - Used to connect to a PC
and control the PDU locally via SSH/Telnet.
H. Daisy Chain (Out) Port – Used for chaining to next PDU.
I. Ethernet Port – Used to connect PDU to the network.
J. Multifunction LCD Readout - Displays various PDU
information such as power and load condition.
K. Select Button - Used to control the LCD screen and toggle
through the available information options.
L. Enter Button - Used to choose selected items, enter to next
level menu or return to previous menu.
M. Outlet Indicator (switched series only) – Indicates if the
outlet is providing power to connected equipment.
Rear Panel Description
A. Ground Stud - Use to ground the PDU.

Technical Specifications

Model Name
Input
Nominal Voltage
Frequency
Maximum Input Current
Plug Type
Power Cord Type
Power Cord Length
Output
Nominal Voltage
Maximum Output Current
Maximum Output Current
Band Number
Outlet Type
Outlet Number
Circuit Breaker
Management and Communications
Multifunction LCD Readout
Software
Networking
Serial Port
Sensor Capable
Physical
Dimensions (H x W x D)
Environmental
Humidity
Altitude
Temperature
Safety Approvals
Certifications
* All specifications are subject to change without notice.
M
M
PDU81003
PDU81007
PDU71003
PDU71007
PDU41003
PDU41007
PDU31003
PDU31007
100-120V
NEMA L5-30P
100-120V
NEMA 5-20R
16
Voltage, Frequency, Load, Current, HW/FW Version, Network Information
3.5" x 17.05" x 4.41"/ 88mm x 433mm x 112mm
7
PDU81008
PDU71008
PDU41008
PDU31008
200-240V
50/60Hz
24A UL (Derated)
NEMA L6-30P
SR (10 AWG)
12 ft/3.65 m
200-240V
24A UL (Derated)
20A (per bank)
2
IEC C13
12 IEC C13/ 4 IEC C19
Yes
PowerPanel® Business Edition
Yes
RJ45
Optional
0 to 95% Non-condensing
11480 ft/3500 m
o
o
o
32
F to 113
F / 0
C to 45
UL 60950-1, FCC Class A
PDU81009
PDU71009
PDU41009
PDU31009
IEC C19
12+4
o
C
10

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents