Siemens FDCIO223 Technical Manual page 66

Input/output module (transponder)
Hide thumbs Also See for FDCIO223:
Table of Contents

Advertisement

Annex
Parameters
Polarity of control and monitoring
systems in relation to one another
Activation period/behavior
Behavior in the event of a
communication problem involving
the control panel
Parameters
Type of input
Monitored for
Input active, when contact is
Filter time
Position
Primary side
Secondary side
66
Building Technologies
Fire Safety
Planning the control line
Input/output 'I/O 1'
□ Same polarity
□ Reverse polarity
□ Permanent
□ Only for the period of: ___ s (1 ... 20 s)
□ Symmetrical pulse pattern
□ Control remains the same as before the error
□ Control is activated
□ Control is deactivated
□ 'Degraded mode horn' function (only possible
with FS20/FS720)
Planning contact input
Input/output 'I/O 1'
□ Danger input
□ Status input
□ Open line
□ Short circuit and open line
□ No monitoring
□ Open
□ Closed
Duration: ____s (0.5 ... 240 s)
Determining the fuses
24 V supply
Input/output 'I/O 1'
Input/output 'I/O 2'
1
The fuse value must be adapted to the respective load.
The maximum specified fuse value must not be exceeded.
Use 'slow-blow' fuses.
Input/output 'I/O 2'
□ Same polarity
□ Reverse polarity
□ Permanent
□ Only for the period of: ___ s (1 ... 20 s)
□ Symmetrical pulse pattern
□ Control remains the same as before the error
□ Control is activated
□ Control is deactivated
□ 'Degraded mode horn' function (only possible with
FS20/FS720)
Input/output 'I/O 2'
□ Danger input
□ Status input
□ Open line
□ Short circuit and open line
□ No monitoring
□ Open
□ Closed
Duration: ____s (0.5 ... 240 s)
One input/output active
Max. 1.5 AT
1
Max. 1.5 AT
1
Max. 1.5 AT
1
Two inputs/outputs active
Max. 2 AT
1
Max. 1 AT
1
Max. 1 AT
1
009122_e1_en_--
2015-10-06