Siemens FDCIO223 Technical Manual page 60

Input/output module (transponder)
Hide thumbs Also See for FDCIO223:
Table of Contents

Advertisement

Specifications
Contact input
Control line
60
Building Technologies
Fire Safety
Measurement voltage
Measurement current
Effective terminating resistances
Line resistance
Line capacitance
Monitored for:
Suppression of erroneous
information
Message evaluation for:
Faults
Ground fault
Message types
Output voltage in active state
Output current per control line in
active state
Monitored for:
Monitoring voltage
Monitoring functions
Monitoring polarity
Suppression of erroneous
information
Message evaluation for:
Faults
Ground fault
Control line resistance
Fusing of control line
Approx. 2 V
Max. 32 mA
3.3 kΩ; +/-1 %; 0.25 W
560 Ω; +/-1 %; 0.25 W
Max. 150 Ω
Max. 1 µF
Short circuit (if configured)
Closed
Deviation in terms of monitoring resistances
Open
Open line
Ground fault monitoring (both inputs/outputs
jointly)
Continuous analysis
1 s (can be increased by the filter time)
60 s
Danger input
Status input
24 V nominal (= secondary-side supply voltage)
Max. 1 A (if two outputs are in use)
Max. 1.5 A (if one output is in use)
Open line (creeping)
Short circuit (creeping)
Ground fault monitoring (both inputs/outputs
jointly)
4 V, unloaded
3.3 kΩ; ±1 %; 0.25 W (reverse polarity)
Manual calibration (identical polarity)
Identical polarity
Reverse polarity
Continuous analysis
1 s (can be increased by the filter time)
60 s
10 % of load resistance;but only up to
max. 150 Ω
Max. 1 AT (to be provided by the customer)
adapted to the load
Characteristics: 'slow-blow'
009122_e1_en_--
2015-10-06