Control With Confirmation - Siemens FDCIO223 Technical Manual

Input/output module (transponder)
Hide thumbs Also See for FDCIO223:
Table of Contents

Advertisement

Structure and function
3.4.3.3

Control with confirmation

40
Building Technologies
Fire Safety
Behavior in the event of an error (control panel-specific)
Error
Failure of 24 V power supply
Error involving control panel (e.g.,
communication with control panel
interrupted)
Notes
In the case of the 'Degraded mode horn' function, the input/output module
accepts the 'Sounder ON' command. This function is only supported on
FS20/FS720 control panels.
The monitoring of monitored control systems will only be resumed 30 seconds
after deactivation.
Control with confirmation is not supported by the following control panels, i.e., the
confirmation is not configured or processed on the control panel:
FC20xx
FC72x
AlgoRex
Configuration option
Open (configuration not possible)
Relay remains unchanged
Relay deactivated
Relay activated
Degraded mode horn function (only
possible with FS20/FS720 control
panels)
009122_e1_en_--
2015-10-06